7 Parameter Description SV600 Series User Manual
78
Function
code
Name
Setting range
Default
Property
P0-03
Main frequency source
X selection
0: Digital setting (preset by P0-08, not save
when power failure)
1: Digital setting (preset by P0-08, save
when power failure)
2: AI1
3: AI2
4: Potentiometer on the keyboard
5: PULSE setting (HDI)
6: Multi-speed instruction
7: Simple PLC
8: PID
9: Communication setting
4
★
Used to select the setting channel of the main frequency. Selections as below:
0: Digital setting (preset by P0-08, not save when power failure)
The initial value of the set frequency is the value of P0-08 (Preset frequency). You can change
the set frequency by pressing the UP and DOWN arrow key on the keyboard (or using the
multi-function DI input terminals with UP/DOWN function).
The frequency after changed would not be saved when power failure. Power on again, the set
frequency still is the setting value in P0-08.
1: Digital setting (preset by P0-08, save when power failure)
The initial value of the set frequency is the value of P0-08 (Preset frequency). You can change
the set frequency by pressing the UP and DOWN arrow key on the keyboard (or using the
multi-function DI input terminals with UP/DOWN function). The changed frequency would be
saved when power failure.When power on agian, the set frequency is the saved frequency.
2: AI1 (0–10 V voltage input)
3: AI2 (0–10 V voltage input or 4–20 mA current input)
When AI is used as the frequency setting source, the corresponding value 100% of the
voltage/current input corresponds to the value of P0-10 (Maximum frequency).
4:Potentiometer on the keyboard
Rotates the potentiometer on the keyboard can increase or decrease the frequency.
5: PULSE setting (HDI)
The frequency is set by HDI. The signal specification of pulse setting is 9–30 V (voltage range)
and 0–100 kHz (frequency range). The corresponding value 100% of pulse setting corresponds
to the value of P0-10 (Maximum frequency).
6: Multi-speed instruction
In multi-speed mode, combinations of different DI terminal states correspond to different set
frequency. SSV600 series inverter supports a maximum of 16 speeds implemented by 16 state
combinations of four DI terminals (allocated with functions 12 to 15) in Group PC. The
multiple references indicate percentages of the value of P0-10 (Maximum frequency). The
related setting of DI terminals, please refer to description of Group P4.
7: Simple PLC