7 Parameter Description SV600 Series User Manual
106
The DO becomes ON when the count value reaches the value set in PB-09.
10: Length reached
The DO becomes ON when the detected actual length exceeds the value set in PB-05.
11: PLC cycle complete
When simple PLC completes one cycle, the DO outputs a pulse signal with width of 250 ms.
12: Accumulative running time arrived
If the accumulative running time of the inverter exceeds the time set in P8-17, the DO becomes
ON.
13: Frequency limited
When the output frequency of the inverter reaches the upper limit or low limit, the DO becomes
ON.
14: Torque limited
In speed control mode, if the output torque reaches the torque limit, the inverter enters the stall
protection state and meanwhile the DO becomes ON.
15: Run Ready
The inverter detects no fault and is ready for RUN, the DO becomes ON.
16: AI1 > AI2
When the input of AI1 is larger than the input of AI2, the DO becomes ON.
17: Upper limit frequency reached
If the running frequency reaches the upper limit, the DO becomes ON.
18: Low limit frequency reached (No output at stop)
If the running frequency reaches the low limit, the DO becomes ON. In the stop state, the DO
becomes OFF.
19: Undervoltage status output
If the inverter is in undervoltage state, the DO becomes ON.
20: Communication setting
Please refer to the MODBUS communication protocol.
21: Reserved
22: Reserved
23: Zero Speed Running 2 (Output at stop)
If the output frequency of the inverter is 0, the DO becomes ON. In the state of stop, the signal
is still ON.
24: Accumulative power-on time arrived
If the inverter accumulative power-on time (P7-13) exceeds the value set in P8-16, the DO
becomes ON.
25: Frequency level detection FDT2 output
Refer to the descriptions of P8-28 and P8-29.
26: Frequency 1 reached
Refer to the descriptions of P8-30 and P8-31.
27: Frequency 2 reached
Refer to the descriptions of P8-32 and P8-33.
28: Current 1 reached
Refer to the descriptions of P8-38 and P8-39.