74 of 116
Customer Work Sheet
LISTING PROGRAMMING SELECTIONS Channel 1
SETTINGS
FACTORY
DEFAULT
PROGRAMMING
OPTIONS
CUSTOMER
SELECTION
SYSTEM INHIBIT
NONE
NONE/ALL
FULL SCALE
100
1.00-10.00
10.0-100.0
100-1999
UNITS
%
%, PPM, PPB NONE
TAG
LEL
UP TO 6 LETTERS,
NUMBERS
OR SYMBOLS
( see footnote 1)
DAMPING(S)
2
0 to 10
ZERP DB(%FS)
0
0 to 5
INHIBIT(mA)
3.6
2.0 to 20
FAULT(mA)
3.5
0.1 to 20.0
CHANNEL INHIBIT
ON
ON/OFF/IHB
COMMON FAIL RLY
-FAILSAFE
YES
NOT
PROGRAMMABLE
COMMON WARN RLY
FAILSAFE
NO
NO/YES
COMMON ALARM RLY
FAILSAFE
NO
NO/YES
COMMON HORN RLY
FAILSAFE
NO
NO/YES
WARN SET POINT
25
.01 to 1999
WARN RESET
20
.01 to 1999