F. Check: The gear motor, if it will not run, the compressor will not run. If no power to it:  Check:
the indicator lights on the circuit board, the bin empty light should be ON, the no water light
should be OFF .

1. If the 

bin empty

 and 

no water

 lights are off, check the

 transformer

a

.

 Transformer "load" side should have 12 to 15 volts.  If not, check the "line" side. 

The line side should have between 208-230 volts. If the line side has the correct

 

voltage and the load side does not, replace the transformer.

2. If the transformer is good, and the 

bin empty

 light is OFF, check the 

ice level sensors

.

a

Remove sensors by sliding them sideways out of the ice chute. Visually inspect

 

them, clean if needed.
b

Look through the ice chute "eye" hole for something blocking the ice chute.

c. If the unit still does not run, replace the ice level sensors.
d

.

 If the bin empty light is still OFF, check the 

circuit board

.

1. Unplug "opto trans" and "LED" connectors from the circuit board.
2. Plug "opto trans" and "LED" connectors from the Scotsman Electronic Control

 

Tester into the circuit board

.

a. Move the "bin full" switch on the tester to the full position. The bin full 
light on the tester should be ON, if not, replace the circuit board.
If the bin full light on the tester is ON, move the tester switch to "bin empty"
the light on the tester should go OFF and the bin empty light on the circuit
 board should go ON. If not, replace the circuit board. If it does as above,
 and the machine still does not run, replace the ice level sensors. 

3

.

 If the transformer is fine, and the "no water" light is ON, check the

 water level sensor.

a. Check the water level in the 

reservoir,

 restore if low. If the water level is ok:

b. Remove the water level sensor from the reservoir and clean the tip if dirty.
////////////////////////////////////////////////////////////////////
CAUTION: THE TIP IS MADE OF GLASS
///////////////////////////////////////////////////////////////////
c

.

 Replace the water level sensor. If the no water light is still on, check that the 

"water sen" plug is firmly plugged into the circuit board. 
d. If the no water light is still on, 

1. Unplug the "water sen" connector from the circuit board.
2. Plug "water sen" connector from the control tester into the circuit board.

a. Move the water switch on the tester to "no water" and the no water light 
on the circuit board should go on. If not, replace the board..
b. Move the water switch to the" water" position, the no water light should 
go off, if  not, replace the circuit board.
c. If after the above, the machine still will not run, replace the
water level sensor

SERVICE DIAGNOSIS: Condition - No Ice Being Produced

STATUS: 

NOTHING OPERATES

MORE INFORMATION ON THE TESTER MAY BE FOUND AT THE END OF THE MANUAL.

NME1850R & FME2400R

January 1995

Page 24

Содержание FME2400R

Страница 1: ...tion Page 11 FOR THE INSTALLER Final Check List Page 12 START UP Page 13 COMPONENT DESCRIPTION Page 14 COMPONENT DESCRIPTION Control Box Page 15 ELECTRICAL SEQUENCE Page 16 OPERATION Water Page 17 OPE...

Страница 2: ...21 3 1 3 1 4 5 9 43 17 8 18 8 There are two separate ice making and refrigeration systems in this model The liquid and discharge lines from each system must go to separate circuits in one remote conde...

Страница 3: ...ck with a water treatment specialist for a water test and recommendations regarding filters and treatment 2 In most cases the water used to make ice should be filtered or treated depending upon the wa...

Страница 4: ...AKER NAMEPLATE LOCATED ON BACK PANEL SERIAL PLATE LOCATED BEHIND FRONT PANEL REMOTE CONDENSERS AND BINS ALSO HAVE MODEL AND SERIAL NUMBERS Model Use with Basic Electrical RCE502 32 1 FME2400R or NME18...

Страница 5: ...later Return the bin to the upright position remove paper covering the bin gasket Install the bin top according to the directions with the bin top Note Do not push bin into position but lift it there...

Страница 6: ...8 inch diameter liquid line and a 1 2 inch diameter discharge line Both ends of each line have quick connect couplings one end has a schrader valve connection that end goes to the condenser Note The o...

Страница 7: ...rked discharge line 3 Begin tightening the couplings together by hand then using two wrenches it is important that ONLY the nut on the precharged lines be turned the other parts of the couplings must...

Страница 8: ...ER Location REMOTE CONDENSER EXCESS PRECHARGED TUBING INSIDE BUILDING ICE MAKER SERVICE ACCESS SERVICE ACCESS SIDE AND BACK ROOF CUTAWAY WALL CUTAWAY CONTACT ROOFING CONTRACTOR NME1850R FME2400R Janua...

Страница 9: ...ity type and 1 4 inch per foot fall is an acceptable pitch for the drain tubing There should be a vent at the highest point of the drain line and the ideal drain receptacle would be a trapped and vent...

Страница 10: ...pressor and the fan motor operates whenever the compressor operates Electrical connections are made at the junction box at the back of the ice maker and at the junction box on the remote condenser The...

Страница 11: ...HARGED REFRIGERANT TUBING A typical installation should generally appear as illustrated below The remote condenser must be located above the ice maker and the precharged lines installed per the instru...

Страница 12: ...sure a minimum of 20 psig 7 Has the machine been secured to the bin 8 Is there a water shut off valve installed near the machine 9 Is the remote condenser installed per local building codes and in a p...

Страница 13: ...n The electrical start up sequence is now on automatic A There should be a short 15 second delay before the gear motor starts B After the gear motor starts the liquid line valve will open the low pres...

Страница 14: ...e Discharge Chute Directs the ice produced by the evaporator into the storage bin Ice Level Sensor An electronic eye it senses the presence of ice in the bottom of the ice discharge chute Operates to...

Страница 15: ...to clear the evaporator of ice when the unit turns off and for the liquid line valve Transformer Supplies low voltage to the circuit board Pump Down Control An automatic reset pressure switch connect...

Страница 16: ...y on and the machine will continue to run unless the ice stays between the sensors for more than 15 seconds bin full At that point the bin empty light goes out and the machine shuts down Shut Down con...

Страница 17: ...through the float valve The water them goes out the bottom of the reservoir tanks to the bottom of the evaporators Reservoir overflow or evaporator condensation is combined into a common drain line an...

Страница 18: ...nt enters an area of relatively low pressure where it can easily boil off or evaporate As it evaporates it absorbs heat from the evaporator and whatever is in contact with it such as the water inside...

Страница 19: ...to the receiver There are two separate refrigeration systems in this machine PUMP DOWN During the pump down cycle usually initiated by the circuit board de energizing the liquid line valve the discha...

Страница 20: ...switch the master switch to OFF 11 After draining the reservoir as in step 6 wash and rinse the water reservoir 12 Go thru steps 13 19 to sanitize the ice machine water system 13 Mix two gallons of sa...

Страница 21: ...ring by removing the ice chute cover unscrewing the ice sweep removing the water shed unscrewing the breaker cover left hand thread unscrewing the auger stud Inspect the assembly looking for wear 4 Cl...

Страница 22: ...more information on removal and replacement of these parts see REMOVAL AND REPLACEMENT Shut off water and electrical supply 1 To remove the auger remove the front and top panels 2 Push back bail clam...

Страница 23: ...ould be moved or the air around it kept cooler Check the fan motor for tight bearings and proper rotation Check that the fan blades are clean and the fan secure to the fan motor shaft b Check the head...

Страница 24: ...If the bin full light on the tester is ON move the tester switch to bin empty the light on the tester should go OFF and the bin empty light on the circuit board should go ON If not replace the circui...

Страница 25: ...frigerant if the unit begins to operate normal low side pressure being about 32 psig stop and look for a leak recover repair replace the drier evacuate and weigh in the nameplate charge If with added...

Страница 26: ...restricted defective or not adjusted properly If needed replace the TXV evacuate and recharge per nameplate 4 Check the insulation on the evaporator It should be dry with no wet spots or frost If the...

Страница 27: ...mble BIN CONTROLS Ice Level Sensors 1 Disconnect electrical power 2 Remove front panel 3 Remove control box cover 4 Locate ice chute at the base of the chute in front of and behind it are two plastic...

Страница 28: ...h spots and damage a The bearing is pressed into the breaker to remove the bearing and replace it an arbor press is needed b Replace lower seals before installing new bearing in breaker Note seals mus...

Страница 29: ...rew auger stud from top of auger c Unscrew 4 allen head cap screws holding breaker to evaporator d Lift up on breaker to remove from auger If the auger is stuck Use a slide hammer type puller to pull...

Страница 30: ...r seal down against it 3 The part of the water seal that rotates with the auger must also be replaced Remove the old part from the auger and clean the mounting area 4 Place a small bead of food grade...

Страница 31: ...etween the gearcase cover and the drip pan gasket Torque the bolts to 110 inch pounds 2 Lower the auger into the evaporator barrel slightly turning it to match up with the drive end Do Not Drop Into t...

Страница 32: ...ding the gear motor to the gear motor plate 3 Remove the gear motor from the ice maker To Inspect the gear motor A Remove the cap screws holding the gear motor case halves together and pry the two cas...

Страница 33: ...es R 404A HP62 refrigerant and polyolester oil Do NOT use mineral oil in this refrigeration system R 404A is a Near Azeotrope so liquid charging is required When the system is serviced a special liqui...

Страница 34: ...Control Note All testing is done with the electrical power on the master switch on and all reset switches reset 1 Unplug photo trans and LED connectors from the circuit board 2 Plug photo trans and LE...

Страница 35: ...the Water position The No Water light on the board should go OFF If not replace the circuit board If the light does go off replace the water level sensor If the Bin Empty light is ON wait 10 20 second...

Отзывы: