background image

schwankgroup.com/schwankair

SchwankAir Controller 

To add program step, select New program step. 

Confirm your selection with the forward arrow. 

Select Day, Night or Off [if the unit should not be in 

operation], set the time for switch on and then for 

which days the program applies, then go to End 

to finish.

A new program step does not replace a set time 

for Day for example, but you can instead select to 

change a program step.

To change a program step, select Change 

program.

The program steps that should not apply are 

removed in Remove program. One or all program 

steps can be removed in the menu.

To return to the factory set basic program, select 

Reset all.

   End 

Tue  10:45

Mon

Tue

Wed

Thu

Fri

Sat

Sun

Tue  10:45

Mon

Tue

Wed

Thu

Fri

Sat

Sun

New program step 7/16

Tue  10:45

00

 :00

Mon

Tue

Wed

Thu

Fri

Sat

Sun

1.

08:00

Day

2.

18:00

Night

3.

10:00

Day

4.

16:00

Night

Tue

10:45

Change program

>Installer menu>Week program

Check program

Change program

Remove program

   End 

Tue  10:45

Mon

Tue

Wed

Thu

Fri

Sat

Sun

Tue  10:45

Mon

Tue

Wed Thu

Fri

Sat

Sun

New program step 7/16

Tue  10:45

00

 :00

Mode

Day

  

 

         ►

New program step 7/16

Tue  10:45

>Installer menu>Week program

Week program on/off

New program step

Check program

>Installer menu>Week program

Check program
Change program

Remove program

Remove program

Remove single

Remove all
Reset all

Fan speed increase

Settings for outdoor temperatures for max

respectively min speed during summer 

respectively winter modes.

Factory setting

T max speed winter: 14°F [-22-59°F]

T min speed winter: 59°F [14-71°F]

T min speed summer: 71°F [59-98°F]

T max speed summer: 98°F [71-122°F]

Make settings for fan mode [see also Operating 

modes section].

Fan settings

>Installer menu>Week program

Week program on/off

New program step
Check program

Week program on/off

•    

  ON

>Installer menu>Week program

>Installer menu

Week program

Fan settings

Heating settings

>Installer menu>Fan settings

Week program

Fan settings

Heating settings

>Installer menu>Fan settings

>Fan speed increase

T max speed winter

T min speed winter
T min speed summer

Week program is activated by selecting On, 

under Week program on/off. In On-mode, a sun, 

moon or Off in the Status window appears to 

indicate day, night respectively Off-function.

Содержание SchwankAir 4000 Series

Страница 1: ...Instructions SchwankAir Controller Heated Models SchwankAir...

Страница 2: ...ing modes Door that is opened and closed The control function notes whether the door is open or closed as standard this mode is default set and is called Fixed flexible the setting is under Installer...

Страница 3: ...rrent stage increases by 1 step If the room temperature is more than 2 degrees above the current setting the current stage decreases by 1 step Summer When the outdoor temperature is greater than the c...

Страница 4: ...7 4 7V 86 F 1 4 3 64 6 4V 86 F 1 5 3 64 6 4V 95 F 2 6 4 81 8 1V 95 F 2 7 5 100 10V 95 F 2 8 5 100 10V 104 F 3 Table Current stage for units with 5 fan step Current stage Fan Stepless fan 5 speeds outp...

Страница 5: ...p door status and day or night mode when week program is used Forward arrow Confirm selection and proceed Rotary dial Scroll between alternatives Back arrow Go back After three minutes the control uni...

Страница 6: ...has been selected System on off Main menu Fan control System on off Installer menu System on off ON Main menu System on off Current settings Displays set room temperature high speed limit speed closed...

Страница 7: ...ernal control General settings Support menu Installer menu To enter the Installer menu code 1932 is entered Select the digits using the rotary dial and confirm using the forward arrow Make settings fo...

Страница 8: ...45 Mon Tue Wed Thu Fri Sat Sun New program step 7 16 Tue 10 45 00 00 Mode Day New program step 7 16 Tue 10 45 Installer menu Week program Week program on off New program step Check program Installer...

Страница 9: ...crease 5 step T max speed summer T max speed winter T min speed summer T min speed winter Outdoor temperature C Fan speed step 1 2 3 0 51 01 52 0 25 30 15 10 5 35 40 T max speed summer T max speed win...

Страница 10: ...ode Fixed time Installer menu Fan settings Door over run Door mode There are three different door modes to choose from Auto Fixed flexible and Fixed open In Fixed flexible mode the control function no...

Страница 11: ...use the Eco functions it is necessary for the valve actuator to be controlled by 0 10V Installer menu Heating settings Eco Comfort Comfort mode Eco mode Installer menu Heating settings Outdoor temp l...

Страница 12: ...pless heat control ON Installer menu Heating settings Return water temp Unit with water heating If there is a demand for the temperature of the return water not to exceed a certain value this function...

Страница 13: ...ngs Last filter change 0 h Unit with water heating Filter alarm is displayed when the set Filter time has been exceeded or when an external filter guard is installed and triggered Filter timer can be...

Страница 14: ...nder External control Activate External on off 0 10V fan control or 0 10V Heating control by selecting On under the relevant one External control BMS Installer menu Filter guard settings External cont...

Страница 15: ...reset Resets values to factory settings Installer menu General settings Function test Factory reset Manual system check Function test Factory reset Manual system check Installer menu General settings...

Страница 16: ...rily intended to prevent the unit from overheating and protect the unit and its surroundings from damages should an overheating occur It will do this by reducing the power output to keep the internal...

Страница 17: ...d when the mixing cabinet is used the dampers is also closed With return temp sensor connected an advanced alarm function occurs At return temperatures less than 59 F the actuator will open regardless...

Страница 18: ...C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C NC Controller Controller External Board Door Contact Switch Room Temp S...

Страница 19: ...5 6 13 14 21 22 ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C NC Controller Co...

Страница 20: ...temperature sensor only valid for water supplied units Filter guard settings Activate filter guard and set service interval External control BMS External on off fan and heating control 0 10V Gateway...

Страница 21: ...g actuator see wiring diagram When several units are connected set a unique ID for each unit 1 9 which Selector of the Air Curtain PCB 3 Power up all units 4 The start up wizard runs and basic settin...

Страница 22: ...sensor Check that nothing is obstructing the unit s air intake and exhaust Check function of the contactors E Check function of actuator and valve flow temperature and bypass settings W Check internal...

Страница 23: ...program Try to reset the alarm Disconnect power set ID 0 and reconnect power to test the Air Curtain PCB pc board result If the unit is running act as if it was an E1 Communication error If it is not...

Страница 24: ...atalabels of your units and contact SchwankAir technical support E12 Room sensor error Fault on or missing external room sensor Room Temp Sensor Optional connected to Air Curtain PCB Try to reset the...

Страница 25: ...to activate system Set parameter Installer menu External control External On Off On 5 6 Outdoor sensor Mandatory Outdoor Temp Sensor included 17 18 Door contact Mandatory External voltfree dry contac...

Страница 26: ...kgroup com schwankair 1 877 686 3779 toll free 1 706 554 6191 csr schwankgroup com schwankgroup com schwankair USA 2 Schwank Way Waynesboro GA 30830 Canada 5285 Bradco Blvd Mississauga ON L4W 2A6 Schw...

Отзывы: