SchwankAir Controller 

E7

Return water

temp. sensor

error.

Fault on or missing, mandatory 

Return water sensor SIReWTA 

connected to Air Curtain PCB.

Try to reset the alarm. Check connections and cable. False errors can 

occur in conjunction with communication error, check that all other 

alarms have been reset. Measure resistance, 47kOhm at 25°C.

Wrong temperature is displayed 

in Controller.

Confirm that WTA is connected to the Air Curtain PCB and securely 

fastened to the return water pipe and compare with what the actual 

temperature is.
Room Temp. Sensor [Optional] - sensor must not be connected to Air 

Curtain PCB when the intention is to use return water sensor. When 

SIReWTA is used, Room Temp. Sensor [Optional] shall be connected 

to the Controller External Board.

E8

Internal

sensor Error

Fault on or missing internal

temperature sensor, SIReIT,

connected to Air Curtain PCB.

Try to reset the alarm. Check connections and cable. False errors can 

occur in conjunction with communication error, check that all other 

alarms have been reset. Measure resistance, 47kOhm at 25°C.

E10

Program error

[different 

programs]

Two or more Air Curtain PCB

in the system have different

programs.

Try to reset the alarm. Controller can control different types of units, 

e.g. Fan heaters or air curtains, water or electrical units, but they 

cannot be combined. The only exception is ambient air curtains in 

combination with either electrical or water heated units of the same 

model. Check the datalabels of your units and contact SchwankAir 

technical support.

E12

Room sensor

error

Fault on or missing external room 

sensor, Room Temp. Sensor 

[Optional] connected to Air 

Curtain PCB.

Try to reset the alarm. Check connections and cable. False errors can 

occur in conjunction with communication error, check that all other 

alarms have been reset. Measure resistance, 47kOhm at 25°C.

E14

Outdoor

sensor error

Fault on or missing, mandatory

outdoor temperature sensor, 

Outdoor Temp. Sensor, 

connected to Controller External 

Board.

Try to reset the alarm. Check connections and cable. False errors can 

occur in conjunction with communication error, check that all other 

alarms have been reset. Measure resistance, 47kOhm at 25°C.

E20

Communication

error

Controller External Board 

[external pcboard]

do not communicate.

Try to reset the alarm. Check connections, modular cables and 

terminals, between all units and components. Systematically shift 

position of communication cables to identify a broken terminal or 

cables.

E21

Room sensor

error

Fault on internal room

temperature sensor in

Controller.

Try to reset the alarm. Check connections and cable. False errors can 

occur in conjunction with communication error, check that all other 

alarms have been reset. If the error is not rectified Controller must be 

replaced.

E22

Multiple control

units connected

Logging tool or an extra control 

unit Controller is connected to 

the system.

Try to reset the alarm. The system will only support one control unit, 

disconnect and reset alarm.

E23

Firmware

error

Components of different releases 

are used in the system.

Make sure all units are from the same release, contact Frico

technical support.

Error code

Cause

Action

Содержание SchwankAir 4000 Series

Страница 1: ...Instructions SchwankAir Controller Heated Models SchwankAir...

Страница 2: ...ing modes Door that is opened and closed The control function notes whether the door is open or closed as standard this mode is default set and is called Fixed flexible the setting is under Installer...

Страница 3: ...rrent stage increases by 1 step If the room temperature is more than 2 degrees above the current setting the current stage decreases by 1 step Summer When the outdoor temperature is greater than the c...

Страница 4: ...7 4 7V 86 F 1 4 3 64 6 4V 86 F 1 5 3 64 6 4V 95 F 2 6 4 81 8 1V 95 F 2 7 5 100 10V 95 F 2 8 5 100 10V 104 F 3 Table Current stage for units with 5 fan step Current stage Fan Stepless fan 5 speeds outp...

Страница 5: ...p door status and day or night mode when week program is used Forward arrow Confirm selection and proceed Rotary dial Scroll between alternatives Back arrow Go back After three minutes the control uni...

Страница 6: ...has been selected System on off Main menu Fan control System on off Installer menu System on off ON Main menu System on off Current settings Displays set room temperature high speed limit speed closed...

Страница 7: ...ernal control General settings Support menu Installer menu To enter the Installer menu code 1932 is entered Select the digits using the rotary dial and confirm using the forward arrow Make settings fo...

Страница 8: ...45 Mon Tue Wed Thu Fri Sat Sun New program step 7 16 Tue 10 45 00 00 Mode Day New program step 7 16 Tue 10 45 Installer menu Week program Week program on off New program step Check program Installer...

Страница 9: ...crease 5 step T max speed summer T max speed winter T min speed summer T min speed winter Outdoor temperature C Fan speed step 1 2 3 0 51 01 52 0 25 30 15 10 5 35 40 T max speed summer T max speed win...

Страница 10: ...ode Fixed time Installer menu Fan settings Door over run Door mode There are three different door modes to choose from Auto Fixed flexible and Fixed open In Fixed flexible mode the control function no...

Страница 11: ...use the Eco functions it is necessary for the valve actuator to be controlled by 0 10V Installer menu Heating settings Eco Comfort Comfort mode Eco mode Installer menu Heating settings Outdoor temp l...

Страница 12: ...pless heat control ON Installer menu Heating settings Return water temp Unit with water heating If there is a demand for the temperature of the return water not to exceed a certain value this function...

Страница 13: ...ngs Last filter change 0 h Unit with water heating Filter alarm is displayed when the set Filter time has been exceeded or when an external filter guard is installed and triggered Filter timer can be...

Страница 14: ...nder External control Activate External on off 0 10V fan control or 0 10V Heating control by selecting On under the relevant one External control BMS Installer menu Filter guard settings External cont...

Страница 15: ...reset Resets values to factory settings Installer menu General settings Function test Factory reset Manual system check Function test Factory reset Manual system check Installer menu General settings...

Страница 16: ...rily intended to prevent the unit from overheating and protect the unit and its surroundings from damages should an overheating occur It will do this by reducing the power output to keep the internal...

Страница 17: ...d when the mixing cabinet is used the dampers is also closed With return temp sensor connected an advanced alarm function occurs At return temperatures less than 59 F the actuator will open regardless...

Страница 18: ...C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C NC Controller Controller External Board Door Contact Switch Room Temp S...

Страница 19: ...5 6 13 14 21 22 ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C NC Controller Co...

Страница 20: ...temperature sensor only valid for water supplied units Filter guard settings Activate filter guard and set service interval External control BMS External on off fan and heating control 0 10V Gateway...

Страница 21: ...g actuator see wiring diagram When several units are connected set a unique ID for each unit 1 9 which Selector of the Air Curtain PCB 3 Power up all units 4 The start up wizard runs and basic settin...

Страница 22: ...sensor Check that nothing is obstructing the unit s air intake and exhaust Check function of the contactors E Check function of actuator and valve flow temperature and bypass settings W Check internal...

Страница 23: ...program Try to reset the alarm Disconnect power set ID 0 and reconnect power to test the Air Curtain PCB pc board result If the unit is running act as if it was an E1 Communication error If it is not...

Страница 24: ...atalabels of your units and contact SchwankAir technical support E12 Room sensor error Fault on or missing external room sensor Room Temp Sensor Optional connected to Air Curtain PCB Try to reset the...

Страница 25: ...to activate system Set parameter Installer menu External control External On Off On 5 6 Outdoor sensor Mandatory Outdoor Temp Sensor included 17 18 Door contact Mandatory External voltfree dry contac...

Страница 26: ...kgroup com schwankair 1 877 686 3779 toll free 1 706 554 6191 csr schwankgroup com schwankgroup com schwankair USA 2 Schwank Way Waynesboro GA 30830 Canada 5285 Bradco Blvd Mississauga ON L4W 2A6 Schw...

Отзывы: