SchwankAir Controller
Outdoor temp. limit
Blocking heating summer time.
Factory setting
Outdoor temp. limit: 59°F [41-86°F]
>Installer menu>Heating settings
Outdoor temp. limit
Eco / Comfort
Open door setp. diff.
Outdoor temp. limit
• 59°F
>Installer menu>Heating settings
Eco / Comfort
Select between Eco and Comfort mode
depending on whether energy savings or optimal
comfort is more important.
Comfort mode gives faster comfort and a slightly
higher output. Comfort mode prioritizes the
temperature comfort, the control system only
accepts a smaller deviation from the set room
temperature.
In ECO-mode several functions and parameter
values are changed, as shown in the display,
which gives lower energy consumption.
For units with internal temperature sensor the
outlet temperature is restricted to 89°F which
further reduces the energy consumption.
Unit with electrical heating
Max heating step is limited.
Unit with water heating
To use the Eco functions it is necessary for the
valve actuator to be controlled by 0-10V.
>Installer menu>Heating settings
Eco / Comfort
• Comfort mode
Eco mode
>Installer menu>Heating settings
Outdoor temp. limit
Eco / Comfort
Open door setp. diff.
Open door setp. diff.
Set by how much the set point value [Room temp.
day/night] is to increase when the door is open.
Factory setting
Set point value difference open door:
3.0K [0K - 10K]
>Installer menu>Heating settings
Eco / Comfort
Open door setp. diff.
Heating step diff.
Open door setp. diff.
•
• 3.0 K
>Installer menu>Heating settings
Heating step diff.
Unit with electrical heating
The temperature difference between connection
of the electrical heating step.
Factory setting
Heating step diff: 1.0K [0K – 10K]
>Installer menu>Heating settings
Open door setp. diff.
Heating step diff.
Heating step limit
Heating step diff.
•
• 1.0 K
>Installer menu>Heating settings
Heating step limit
Unit with electrical heating
Possibility of limiting the heating.
Factory setting
Heating step limit: 2/3 [1-2/3]
>Installer menu>Heating settings
Heating step diff.
Heating step limit
Sensor calibration
Heating step limit
•
• 3
>Installer menu>Heating settings