SchwankAir Controller
Sensor calibration
If the sensor displays the wrong values these can
be calibrated. Some display errors may occur,
but this is primarily due to the location [cold/hot
surfaces etc]. The value + or – adds to or subtracts
from the measured value [for e2K gives
an increase of the displayed value of 2 degrees].
Factory setting
Room temperature sensor: 0.0K [-10K – 10K]
Outdoor temperature sensor: 0.0K [-10K – 10K]
>Installer menu>Heating settings
Heating step limit
Sensor calibration
Stepless heat control
Room temp. sensor
Outdoor temp. sensor
>Installer menu>Heating settings
>Sensor calibration
Room temp. sensor
•
0.0 K
>Installer menu>Heating settings
>Sensor calibration
Stepless heat control
Unit with electrical heating
For stepless control of electrical heating, for
example via external triac.
Unit with water heating
To use Advanced fully, stepless heat control must
be used.
Stepless heat control: ON [Off - not selectable]
>Installer menu>Heating settings
Sensor calibration
Stepless heat control
Control range limit
Stepless heat control
•
3
>Installer menu>Heating settings
>Installer menu>Heating settings
Sensor calibration
Stepless heat control
Control range limit
Stepless heat control
• ON
>Installer menu>Heating settings
Return water temp.
Unit with water heating
If there is a demand for the temperature of the
return water not to exceed a certain value, this
function is activated under Return water temp.
A return water temperature sensor [proximity
sensor, option] must then be installed on the return
water pipe.
Install Return temp. Sensor to Connected and
select max return temperature [59-194°F] using the
turn wheel. During operation, this function limits
the valve’s degree of opening, which reduces the
flow and the return temperature.
Factory setting
Return temp. sensor: Not connected [Connected]
Return temp. limit: Off [59-194°F]
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Return temp. limit
Return temp. limit
•
OFF
Installer menu>Heating
settings>Return water temp.
>Installer menu>Heating settings
Sensor calibration
Return water temp.
Stepless heat control
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Return temp. limit
Room temp. sensor
• Not connected
Installer menu>Heating
settings>Return water temp.
Connected
Control range limit
The maximum room temperature that a user
can select is limited to between [41-95°F].
Factory setting
Control range limit temperature: 95°F [41-95°F]
>Installer menu>Heating settings
Sensor calibration
Stepless heat control
Control range limit
Control range limit
•
95
ºF
>Installer menu>Heating settings