Doors that are always or often left 

open for longer periods

If a door is always, or often, left open it is possible 

to use a function called CURRENT STAGE instead. 

The fan and heating steps increase/decrease 6 or 

9 steps [depending on the type of unit] and are 

only controlled by the room temperature. Actual 

Current stage is shown in the status screen. The 

function current stage is activated in two ways:

When the door is closed - over run

When the door has been closed, high speed 

mode remains during the fixed time that is set 

under Installer menu > Settings fan > Door over 

run > High speed over run and at low speed 

during a fixed time under Installer menu > Settings 

fan> Door over run > Low speed over run, on 

the condition that it is sufficiently warm in the 

premises, otherwise the fans run until the desired 

temperature has been reached.

When the door is closed, the set point value

shifts from room tempe fixed set point 

value difference for open door to Room temp.

day/night.

Over run is factory set so that the over run

times are controlled according to how often

the door is opened [Auto mode under Installer

menu > Settings fan > Door over run >

Over run mode].

Doors that are always open

For a door that is always open, door mode

Fixed open > can be selected under Settings

fan > Door mode.

Doors that are often open

For a door that is often open Auto can be

selected under Installer menu > Settings fan 

> Door mode. In Auto mode, the control 

automatically switches between Fixed flexible and 

Fixed open modes depending on how often the 

door has been open [when the door has been 

open for longer than 300 seconds the function 

changes from Fixed Flexible to Fixed Open].

schwankgroup.com/schwankair

Operating modes

Door that is opened and closed

The control function notes whether the door is

open or closed as standard, this mode is default

set and is called Fixed flexible [the setting is under 

Installer menu > Settings fan > Door mode].

Open door

Indicates OP on the installer status screen.

Fan control runs at high speed mode and is 

controlled to outdoor temperature.

During dropping outdoor temperatures during 

the winter and increasing outdoor temperatures 

during summer the fan speed increases.

High speed limit is set under Main Menu > Fan 

control > High speed limit. The control curves to 

the outdoor temperature are set under Installer 

menu > Settings fan > Fan speed increase where 

temperatures for min- and max speed are set 

for summer and winter modes. Normally it is 

requested that heat is engaged when the door 

is opened. The set point value [Room temp. day] 

is then increased with the fixed set point value 

difference that can be changed under Installer 

menu> Settings heating > Open door setp. diff., 

factory setting 3.0 K. The set point is set under 

Main Menu > Temperature settings > Room temp. 

day. If week program is used the night time set

point value is set under Main menu > Temp.

settings > Room temperature night. The room

temperature is regulated using the integrated

room temperature sensor or the external room 

temperature sensor.

Closed door

Indicated CL on the installer status screen.

When heating demand the fan speed runs at low 

speed which is set under Main menu > Fan speed 

> Speed closed door. Heating is regulated to 

Room temp. Day which is set under Main Menu > 

Temperature settings > Room temp. day.

If week program is used the night time set point 

value is regulated against the Room temperature 

is set under Main menu > Temp. settings > Room 

temperature night. The room temperature is 

regulated using the integrated room temperature 

sensor or the external room temperature sensor.

SchwankAir Controller 

Содержание SchwankAir 4000 Series

Страница 1: ...Instructions SchwankAir Controller Heated Models SchwankAir...

Страница 2: ...ing modes Door that is opened and closed The control function notes whether the door is open or closed as standard this mode is default set and is called Fixed flexible the setting is under Installer...

Страница 3: ...rrent stage increases by 1 step If the room temperature is more than 2 degrees above the current setting the current stage decreases by 1 step Summer When the outdoor temperature is greater than the c...

Страница 4: ...7 4 7V 86 F 1 4 3 64 6 4V 86 F 1 5 3 64 6 4V 95 F 2 6 4 81 8 1V 95 F 2 7 5 100 10V 95 F 2 8 5 100 10V 104 F 3 Table Current stage for units with 5 fan step Current stage Fan Stepless fan 5 speeds outp...

Страница 5: ...p door status and day or night mode when week program is used Forward arrow Confirm selection and proceed Rotary dial Scroll between alternatives Back arrow Go back After three minutes the control uni...

Страница 6: ...has been selected System on off Main menu Fan control System on off Installer menu System on off ON Main menu System on off Current settings Displays set room temperature high speed limit speed closed...

Страница 7: ...ernal control General settings Support menu Installer menu To enter the Installer menu code 1932 is entered Select the digits using the rotary dial and confirm using the forward arrow Make settings fo...

Страница 8: ...45 Mon Tue Wed Thu Fri Sat Sun New program step 7 16 Tue 10 45 00 00 Mode Day New program step 7 16 Tue 10 45 Installer menu Week program Week program on off New program step Check program Installer...

Страница 9: ...crease 5 step T max speed summer T max speed winter T min speed summer T min speed winter Outdoor temperature C Fan speed step 1 2 3 0 51 01 52 0 25 30 15 10 5 35 40 T max speed summer T max speed win...

Страница 10: ...ode Fixed time Installer menu Fan settings Door over run Door mode There are three different door modes to choose from Auto Fixed flexible and Fixed open In Fixed flexible mode the control function no...

Страница 11: ...use the Eco functions it is necessary for the valve actuator to be controlled by 0 10V Installer menu Heating settings Eco Comfort Comfort mode Eco mode Installer menu Heating settings Outdoor temp l...

Страница 12: ...pless heat control ON Installer menu Heating settings Return water temp Unit with water heating If there is a demand for the temperature of the return water not to exceed a certain value this function...

Страница 13: ...ngs Last filter change 0 h Unit with water heating Filter alarm is displayed when the set Filter time has been exceeded or when an external filter guard is installed and triggered Filter timer can be...

Страница 14: ...nder External control Activate External on off 0 10V fan control or 0 10V Heating control by selecting On under the relevant one External control BMS Installer menu Filter guard settings External cont...

Страница 15: ...reset Resets values to factory settings Installer menu General settings Function test Factory reset Manual system check Function test Factory reset Manual system check Installer menu General settings...

Страница 16: ...rily intended to prevent the unit from overheating and protect the unit and its surroundings from damages should an overheating occur It will do this by reducing the power output to keep the internal...

Страница 17: ...d when the mixing cabinet is used the dampers is also closed With return temp sensor connected an advanced alarm function occurs At return temperatures less than 59 F the actuator will open regardless...

Страница 18: ...C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C NC Controller Controller External Board Door Contact Switch Room Temp S...

Страница 19: ...5 6 13 14 21 22 ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C2 X5 C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V C NC Controller Co...

Страница 20: ...temperature sensor only valid for water supplied units Filter guard settings Activate filter guard and set service interval External control BMS External on off fan and heating control 0 10V Gateway...

Страница 21: ...g actuator see wiring diagram When several units are connected set a unique ID for each unit 1 9 which Selector of the Air Curtain PCB 3 Power up all units 4 The start up wizard runs and basic settin...

Страница 22: ...sensor Check that nothing is obstructing the unit s air intake and exhaust Check function of the contactors E Check function of actuator and valve flow temperature and bypass settings W Check internal...

Страница 23: ...program Try to reset the alarm Disconnect power set ID 0 and reconnect power to test the Air Curtain PCB pc board result If the unit is running act as if it was an E1 Communication error If it is not...

Страница 24: ...atalabels of your units and contact SchwankAir technical support E12 Room sensor error Fault on or missing external room sensor Room Temp Sensor Optional connected to Air Curtain PCB Try to reset the...

Страница 25: ...to activate system Set parameter Installer menu External control External On Off On 5 6 Outdoor sensor Mandatory Outdoor Temp Sensor included 17 18 Door contact Mandatory External voltfree dry contac...

Страница 26: ...kgroup com schwankair 1 877 686 3779 toll free 1 706 554 6191 csr schwankgroup com schwankgroup com schwankair USA 2 Schwank Way Waynesboro GA 30830 Canada 5285 Bradco Blvd Mississauga ON L4W 2A6 Schw...

Отзывы: