schwankgroup.com/schwankair
SchwankAir Controller
External filter guard
Unit with water heating
If an external filter guard, e.g. a pressure switch,
is used, it is activated under External filter guard,
select On.
Factory setting
External filter guard: Off [On]
>Installer menu
Filter timer setting
External filter guard
Last filter change
Last filter change
To check the number of run time hours since the
last filter replacement, select Last filter change.
The time is reset when the filter alarm is reset. If
the time is to be reset before the alarm has gone,
switch the filter timer on and off.
>Installer menu>Filter guard settings
Filter timer setting
External filter guard
Last filter change
>Installer menu>Filter guard settings
Last filter change
0 h
Unit with water heating
Filter alarm is displayed when the set Filter time has
been exceeded or when an external filter guard is
installed and triggered.
Filter timer can be used as a Service interval timer
for electrical heated units when filter is not allowed.
Filter guard settings
>Installer menu
Heating settings
Filter guard settings
External control
Filter timer on/off
Filter alarm is activated by selecting On, under
Filter timer on/off.
Factory setting
Filter timer on/off: Off [On]
Filter timer setting
Under Filter timer setting, set the desired run time
to between 50 and 9950 hours.
Filter timer setting: 1500 h [50 - 9950 h]
>Installer menu>Filter guard settings
Filter timer on/off
Filter timer setting
External filter guard
>Installer menu>Filter guard settings
Filter timer on/off
Filter timer setting
External filter guard
Filter timer setting
•
•
1500 h
>Installer menu>Filter guard settings