Functional description
30
03.00 | RSS R1/W1 | Assembly and Operating Manual | en | 0889125
If the DIP switch is switched back without the POTI value having
changed outside of its ‘oscillation range’, no new value is accepted
as system time or limit value (to avoid faulty operations).
6.1.11 Setting the output behaviour
Functional change of the output signal D01
DIP6 = ON:
Output D01 will not be received as at radio transmitter, but is
“NOT D02”.
6.1.12 Teaching the limit value (teaching threshold)
Analog value currently sent – 0.5V
DIP7:
The current value of the analog value minus 0.5 V is accepted as
limit value for the battery monitoring.
6.1.13 Setting the watchdog time
Einst. Poti
2,5 V
dec 255
limit value setting
0
0,0
0
50
1,8
127
100 %
3,6 U N
255 dec
batt
set up Poti
t
system
1s (8=OFF)
35s (8=ON)
System time setting
set up Poti
Setting the watchdog time
The POTI value is saved by turning on of the DIP switch 4 at status
“ACTIVE” and “WATCHDOG”. During the set-up mode (DIP 4
moved), the LED responds directly to a changing POTI value (and
DIP 8 setting) by changing the blinking frequency.
The setting occurs using the “System time setting” characteristic
curve. System time = f (DIP8 and POTI value). The acceptance oc-
curs only when DIP 4 is switched back.
If the DIP switch is switched back without the POTI value having
changed outside of its ‘oscillation range’, no new value is accepted
as system time or limit value (to avoid faulty operations).