OPERATING INSTRUCTIONS
9
CG700 rondo
Version: 27202 -
D
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany
4.2
Planning the pump pit
When planning a pump duct take into account:
1. Clear dimensions min. 1000 x 600 x 600
2. Return connection min. 300 mm under the pool water level
3. Leakage water discharge pipe-end min. DN 40
4. Cooling air supply for the motor min. 2x DN 125. Minimum clearance of the motor
cooling air inlet to the wall = 200 mm.
5. Be sure to cover the pump pit if it is installed in the open air.
6. The position of the non-return air valve (L) must always be over the pool water level
(BWSP).
7. The position of the switchgear cabinet (S) must always be over the pool water level
(BWSP).
8. In case of leakage from the pump, a suitable water drainage must be provided!
fig. 9: Cross-sectional view of the pump
pit
fig. 10: Top view of the pump pit
BWSP
Pool water level
L
Air valve
S
Switchgear cabinet
Warning! Mortal danger!
The mains power supply cable must be equipped with an all-pole separator
with a contact opening of 3 mm.
8216
8217