ExMax-...-Y.., RedMax-...-Y..

PA

PA

PA

PA

 3-sec. mode, 3-pos-operation, heating by low ambient temperatures

Schischek GmbH 

Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax  ++49 (0)9101-908177, Email [email protected]

ExMax-.. and RedMax-.. extra information EL - size S

Self adjustment:

To adjust the signal input/output to the Angle

of rotation of the damper/valve the button T

must be pushed for minimum 3 sec.

Function of switch a and b:

a

 closed,  On (Off) - in acc. to left/right mounting ot the actuator

b

 closed,  Off (On) - in acc. to left/right mounting ot the actuator

Self adjustment:

To adjust the signal input/output to the Angle

of rotation of the damper/valve the button T

must be pushed for minimum 3 sec.

Self adjustment:

To adjust the signal input/output to the Angle

of rotation of the damper/valve the button T

must be pushed for minimum 3 sec.

Self adjustment:

To adjust the signal input/output to the Angle

of rotation of the damper/valve the button T

must be pushed for minimum 3 sec.

Function of switch a and b:

a

 closed,  On (Off) - in acc. to left/right mounting ot the actuator

b

 closed,  Off (On) - in acc. to left/right mounting ot the actuator

E X P L O S I O N P R O O F

Wiring alternatives for modulating actuators with or without spring return

Modulating or 3-pos with/without spring return

1

Y

mA

2

T

3

U

mA

4

5

Y

VDC

U

VDC

6

I

VDC/mA

1

2

3

4

~

-

~

+

PE

heater

5

a

b

24...230 VAC/DC

Modulating with/without spring rturn

1

Y

mA

2

T

3

U

mA

4

5

Y

VDC

U

VDC

6

I

VDC/mA

1

2

3

4

~

-

~

+

PE

heater

5

24...230 VAC/DC

3-pos with/without spring return, plus feedback

1

2

T

3

U

mA

4

5

U

VDC

6

I

VDC/mA

1

2

3

4

~

-

~

+

PE

heater

5

a

b

24...230 VAC/DC

Modulating with/without spring return, no feedback

1

Y

mA

2

T

3

4

5

Y

VDC

6

I

VDC/mA

1

2

3

4

~

-

~

+

PE

heater

5

24...230 VAC/DC

I

Reverse function:

bridge 3--4 reverse input and output

signals.

I

I

I

Selection of running time for spring return:

Standard wiring = spring return in ~10 Sek

Additional wiring terminal 5 = spring return in ~ 3 Sek

Reverse function:

bridge 3--4 reverse input and output

signals.

Selection of running time for spring return:

Standard wiring = spring return in ~10 Sek

Additional wiring terminal 5 = spring return in ~ 3 Sek

Reverse function:

bridge 3--4 reverse input and output

signals.

Selection of running time for spring return:

Standard wiring = spring return in ~10 Sek

Additional wiring terminal 5 = spring return in ~ 3 Sek

Reverse function:

bridge 3--4 reverse input and output

signals.

Selection of running time for spring return:

Standard wiring = spring return in ~10 Sek

Additional wiring terminal 5 = spring return in ~ 3 Sek

B

A

B

A

B

A

B

A

SB 5.0

SB 5.1

SB 5.3

SB 5.2

I. Operation with 3 sec. motor running time mode

While operating the ExMax actuator in 3 sec. mode following parameters have to be aligned:

1. Maximum cyclic duration 10%  ED, maximum 1 cycle/min.

2. Exeeding above mentioned parameter the actuator will remain functionless until cooling

    has occured. At 2 wire mode (circuit diagram SB 2.1 / 7.0 / 7.2) the cool down is

funtionless. The cool down must be guaranteed by control system.

3. The actuator must be operated with an outside load of at least 3 Nm.

4. After installing the actuator to the damper/armature an automatic alignment has to be 

    accomplished, in order to obtain a "gentle blockade/stop". This function protects the

    damper/armature by reducing the end positions/blockade speed in order to avoid 

mechanical overload. The actuator alignes specifically once with 30 Sec/90° onto each

position, recognizes the blockade position in order to reduce the motor performance 

during operation briefly before reaching the end /blockade position.

II. 3-pos operation

ExMax (RedMax) actuators are in the best way suitable for the 3-pos operation.To  protect

such elements as gears and mounting elements against harmful influences like minimum

pulse time, ExMax (RedMax) actuators are protectet via internal electronics. The internal

electronic permits 20 impulses with < 0.5 > sec. cyclic duration, afterwards at least

1 impulse  > 1 sec. must follow. If clocked with more than 20 impulses each < 1 sec. the

actuator will adjust into a suspend mode.There after a reset is mandadory and will be

achieved by briefly switching of the supply voltage for about 2 sec..The controll unit has

to be parameterized  in order to be set within the above mentioned  duration limits.

III. Use at low ambient temparature below - 20°C

All ExMax (Redmax) actuators are equipped with a regulated integrated heating device
designed for employments down to -40°C ambient temperature.

The heater will be supplied automatically by connecting the constant voltage supply on

the clamps 1 and 2.

Following parameters are to be considered by ambient temperaure < 10°C:

1. After mounting the actuator must bei immediately electrically connected.

2. The actuator will only be activated after the operating temperature has reached at least

    -20°C .

3. The adjustment options are only ensured after this heating up period.

www.schischek.com

Содержание RedMax-...-BF-CT

Страница 1: ...or 10 sec at 90 On off 3 pos 2 contacts 5 85 EEx i circuit SB 7 0 7 1 RedMax 15 BF 15 Nm 24 230VAC DC 3 15 30 60 120 sec at 90 3 or 10 sec at 90 On off 3 pos 2 contacts 5 85 EEx i circuit SB 7 0 7 1 RedMax VA Type as above but with stainless steel housing AISI 316 for aggressive ambient 12x12 shaft shaft manual override cable glands and hollow rivet nickel plated RedMax CT Type as above but with A...

Страница 2: ...on Axle of the actuator double squared 12 x 12 mm direct coupling 100 overload protected and 100 self locking up to 15 Nm Electrical connection cable 1 m diameter of wires 0 5 mm for connection inside hazardous areas an terminal box is required Diameter of cable Æ 9 6 mm Æ 6 2 mm Cable gland M16 x 1 5 standard cable and wire entries are integral part of explosions proof encapsulation tested acc to...

Страница 3: ...same like supply of the actuator on same fuse 5 8 9 10 85 11 1 2 3 PE heater 5 24 230 VAC DC FireSafe 4 Attention If you use this type of wiring the heater does not work in case of open contact a b EEx i intrinsic safe data If 3 sec mode is selected the self adju stment ofAngle of rotation must be started and operation mode of max 10 ED must be guaranteed Never use actuators in this mode without e...

Страница 4: ...rection of the spring return function by left right mounting In acc to the actuator type 5 different motor running times and 2 different spring return running times can be selscted on site The integral heater is for ambient temperatures down to 40 C C Working with 3 sec motor running time See extra information EL D 3 pos control mode See extra information EL E Spring return Spring return function ...

Страница 5: ...it length in m Factor 0 0714 drive specific factor Vmm m based on the electrical conductivity of electrolytic copper with a coefficient of 56m Wmm pannel length L m terminal box actuator line cross section A mm voltage Uv V Formula for max cable length L at cable cross section A L A l Uv 18V 0 0714 Formula of needed cable cross section A at a cable length of L A 0 0714 l L Uv 18V The EL data sheet...

Страница 6: ...ate actuator in the 3 sec mode without an outside load of min 3 Nm Engaging 1 wire On Off controlls in the 3 sec modus with spring return the ac tuator can only be operated with 1 On Off function per minute otherwise electronics will be liable to overheating Attention If you use this type of wiring the heater does not work in case of open contact Attention If you use this type of wiring the heater...

Страница 7: ...se function bridge 3 4 reverse input and output signals Selection of running time for spring return Standard wiring spring return in 10 Sek Additional wiring terminal 5 spring return in 3 Sek B A B A B A B A SB 5 0 SB 5 1 SB 5 3 SB 5 2 I Operation with 3 sec motor running time mode While operating the ExMax actuator in 3 sec mode following parameters have to be aligned 1 Maximum cyclic duration 10...

Страница 8: ...tor sits diagonally on the squared damper shaft l The actuators have an angle of rotation of 95 inclusive 5 pre tention While assembling the pre loading was not considered l Dismount actuator of the damper use the enclosed socket wrench to draw up approx 5 over the hand operated control device before remounting on the damper shaft Consider additional information ME of the assembly instructions 09 ...

Страница 9: ... inl radius of bend for the cable All ExMax and RedMax actuators are equipped with a 10 position switch a push button and a multicolor LED for calibration These control elements are to be found cable laterally behind the two middle sectioned dummy plugs For operation these must be removed The calibration can be achieved despide lining up tension at the actuator The explosion prevention is not impa...

Страница 10: ...with drill template on the damper or to a mounting bracket 2 Adjust drive shaft of the actuator with the socket wrench that the drive stands perpendicular to the damper before pluging actuator on to the damper shaft 3 Plug actuator onto damper shaft and fix diagonally with 2 screws 4 Remove the socket wrench 5 Pivot and tighten the remaining screws Note the drive shaft is selflockingly produced an...

Страница 11: ...ire dampers Mounting to a ball valve Mounting to a butterfly valve Fire damper Assembly It is to be considered that the actuators have a total angle of rotation of approx 95 in order to realize a pre tention on the damper Therefore thr actuator sits tilted on the damper shaft In order to prevent this and to assure pre tention to the damper the driving shaft has to be adjusted mechanically before c...

Страница 12: ...ssory to the actuator Mounting of terminal boxes type ExBox RedBox via mounting bracket type MKK S to the actuator accessory 1 Put the squared connection part to the actuator then mount ExSwitch RedSwitch and fix it with 4 screws 2 ExMax RedMax with mounted ExSwitch RedSwitch 4 x 1 Screw mounting bracket MKK S to the actuator A then terminal box to the mounting bracket B schrauben 2 x 2 x B A Moun...

Отзывы: