ExMax-...-F, ExMax-...-SF, RedMax-...-F, RedMax-...-SF
PA
PA
ExMax-...-BF, RedMax-...-BF
PA
PA
PA
U
0
= 10,6 V
I
0
= 11 mA
P
0
= 30 mW
C
i
= 0
L
i
= 0
IIC
IIB
IIA
C
0
830 nF 3,7µF 4,5 µF
L
0
2 mH
5 mH 10 mH
Schischek GmbH
Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax ++49 (0)9101-908177, Email [email protected]
ExMax-.. and RedMax-.. extra information EL - size S
E X P L O S I O N P R O O F
Wiring alternatives for on-off and 3-pos actuators with spring return
On-off and 3-pos
1
2
3
4
~
-
~
+
PE
heater
5
24 to 230 VAC/DC
a
b
If 3 sec. mode is selected, the self adju-
stment of angel of rotation must be started
and operation mode of max. 10% ED
must be guaranteed.
Never operate actuator in the 3 sec mode
without an outside load of min. 3 Nm.
Engaging 1 wire On/Off controlls in the
3 sec. modus with spring return, the ac
tuator can only be operated with 1 On/Off
function per minute otherwise electronics
will be liable to overheating.
Attention!
!
!
On-off 1-wire
1
2
3
4
~
-
~
+
PE
heater
5
24 to 230 VAC/DC
a
Wiring alternatives for BF actuators
On-off 1-wire - spring EEx-i circuit
1
2
°C
push button
6 7
< 5 °
8
9 10
> 85 °
11
1
2
3
~
-
~
+
PE
heater
5
24...230 VAC/DC
FireSafe
4
O-off/3-pos - spring EEx-i circuit
1
2
°C
6 7
< 5 °
8
9 10
> 85 °
11
1
2
3
~
-
~
+
PE
heater
5
24...230 VAC/DC
FireSafe
4
a
b
On-off 1-wire - spring EEx-d limiter
1
2
°C
Push button
The intrinsic safe circuit must
be closed otherwise the
actuator is unable to work!
6 7
< 5 °
8
9 10
> 85 °
11
1
2
3
~-
~+
PE
heater
5
24...230 VAC/DC
4
Limiter
Values of the EEx-i circuit
Achtung!
!
!
EXC-DS1/VA
If 3 sec. mode is selected, the self adju-
stment of angel of rotation must be started
and operation mode of max. 10% ED
must be guaranteed.
Never operate actuator in the 3 sec mode
without an outside load of min. 3 Nm.
Engaging 1 wire On/Off controlls in the
3 sec. modus with spring return, the ac
tuator can only be operated with 1 On/Off
function per minute otherwise electronics
will be liable to overheating.
! Attention !
If you use this type of
wiring the heater does
not work in case of
open contact.
! Attention !
If you use this type of
wiring the heater does
not work in case of
open contact.
! Attention !
If you use this type of
wiring the heater does
not work in case of
open contact.
Standard wiring = spring return in ~10 sec.
Additional wiring terminal 5 = spring return in ~ 3 sec.
Standard wiring = spring return in ~10 sec.
Additional wiring terminal 5 = spring return in ~ 3 sec.
Standard wiring = spring return in ~10 sec.
Additional wiring terminal 5 = spring return in ~ 3 sec.
Standard wiring = spring return in ~10 sec.
Additional wiring terminal 5 = spring return in ~ 3 sec.
Standard wiring = spring return in ~10 sec.
Additional wiring terminal 5 = spring return in ~ 3 sec.
Integrated aux. switches
max 24V/3A, 230V/0,5A
switching at 5° and 85°.
Supply at aux. switches must
be the same like supply of the
actuator on same fuse in case
that power is switched.
Integrated aux. switches
max 24V/3A, 230V/0,5A
switching at 5° and 85°.
Supply at aux. switches must
be the same like supply of the
actuator on same fuse in case
that power is switched.
Integrated aux. switches
max 24V/3A, 230V/0,5A
switching at 5° and 85°.
Supply at aux. switches must
be the same like supply of the
actuator on same fuse in case
that power is switched.
EEx-i circuit for
p potential free
push button on site
and safety temperature sensor
(Type
FireSafe
accessories)
EEx-i circuit for
p potential free
push button on site
and safety temperature sensor
(Type
FireSafe
accessories)
push button
B
A
B
A
B
A
SB 2.0
SB 2.1
SB 7.0
SB 7.1
SB 7.2
www.schischek.com