Technical data

RedMax-5.10-BF

RedMax-15-BF

Accessories or special solutions - size S

Schischek GmbH 

Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax  ++49 (0)9101-908177, Email [email protected]

RedMax-5.10-BF

RedMax-15-BF

Special makes

RedMax-..-VA/-CT

E X P L O S I O N P R O O F

Certification

PTP 04 ATEX 2106

ATEX

Directive 94/9/EG (ATEX)

Approval for gas

II3G EEx nC II T6 II3(1)G EEx [ia] IIC gas, mist, vapour,   
zone 2

Approval for dust

II3D IP66 T80°C  dust, zone 22

Identification

CE Nr. 0158

EMC

EMC-directive 89/336/EG

Low voltage

Low-voltage directive 72/23/EG

IP-Protection

IP 66

Potential compensation

external PA-terminal, 4 mm²

EEx-i circuit data

see table below wiring diagrams

Torque motor

5 / 10 Nm selectable on site

15 Nm

Torque spring return (F)

min. 10 Nm

min. 15 Nm

Dimension of external torque

above mentioned torques are min. torques in blocked position, eternal torque should be max. 80%  of max. actuator torque but min. 3 Nm

Supply voltage/Frequency

24...230 VAC/DC,  + 15 % / - 20% , self adaptable, Frequency 50...60 Hz +/- 20 %

Dimension

max. starting currents see table (in acc. with voltage, I 

start 

>> I 

rated

), max. 20 W blocking position, approx. 16 W for heater

Protection class

class I (grounded)

Angle of rotation and indication

95°,  incl. ~ 5° pre-tention, mechanical value indication

Working direction

selectable by left/right mounting to the damper/valve shaft

Motor running time

3 / 15 / 30 / 60 / 120 sec. at 90° selectable on site

3 sec. mode - motor

In acc. with the supply voltage rand external torque 3 to 4 sec at 90° angle of rotation

Motor

brushless DC Motor

Spring return (F)

spring return in the event of loss of power

Spring return running time (F)

spring return in 3 sec., or 10 sec. at 90°, selectable on site

3 sec. mode - spring return

in acc. with external torque 3 to 4 sec. at 90° angle of rotation

Safety operations at 10 sec (F)

min. 10.000 in acc. with construction of damper and ambient

Safety operations at   3 sec (F)

min.   1.000 in acc. with construction of damper and ambient

Response time spring return

up to 1 sec. after power  failure

Control mode

On-off and 3-pos  in acc. with wiring, selectable on site

Intrinsic safe circuit

Additional EEx-i circuit to connect a passive potential free thermostat as a safety sensor, e.g. type FireSafe

Integratet aux. switches

2 aux. switches, switching at 5° and 85° Angle of rotation

Axle of the actuator

double squared 12 x 12 mm, direct coupling, 100 % overload protected and 100 % self locking up to 15 Nm

Electrical connection

cable, ~1 m, diameter of wires 0,5 mm² for connection inside hazardous areas an terminal box is required!

Diameter of cable

Æ

  9,6  mm + ~ 

Æ

  6,2  mm

Cable gland

M16 x 1,5 standard - cable - and wire entries are integral part of explosions proof encapsulation; tested acc. to EN 50018

Manual override

Use Manual override only if supply voltage is cut, use delivered socket wrench, slow motion, enough torque/force is required

Attention:

 with manual operation of the spring danger of injury exists, with release/let go the hexagonal spanner!

Integral heater

integral heater, controlled, for ambient temperature down to  - 40°C

Housing material

Aluminium die cast housing, painted (optional in stainless steel version AISI 316 - type RedMax-...

-VA, 

amercoat painting type RedMax

 ...-CT

)

Dimensions

l x w x h 210 x 95 x 80 mm, for diagramm see extra information “ME”

Weight

~ 3,5 Kg Aluminium housing  (stainless steel ~ 7 Kg)

Ambients

storage temp. - 40..+ 70°C, working temperature  - 40..+ 40°C at T6 and  - 40...+ 50°C at T5, humidity in acc. with EN 60335-1

Operation mode at
runningtime motor 3 sec

at 3 sec. 10 % ED, max. 1 on-off cycle per minute (must be guaranteed by control system)

Operation mode ex
runningtime motor 15 sec

at 15/30/60/120 sec. 100 % ED

Self adjustment

if you select 3 sec. and 15 sec. mode for motor you need to start the self adjustment mode

Maintenance

maintenance free, maintenance must be complied with regional standards, rules and regulations

Wiring diagrams (SB)

SB 7.0 / 7.1

SB 7.0 / 7.1

Delivery

1 actuator, 1 m cable, double squared shaft connection 12x12 mm, 4 screws M 4 x 100, 4 nuts M 4
socket wrench for simple manual override

Parameter at delivery

5 Nm, 30 sec./90°

15 Nm, 30 sec./90°

Explosion proof

RedMax actuators  - size S

RedMax-..-VA

above listed types in stainless steel version, housing AISI 316.

RedMax-..-CT

above listed types in Al-housing with amercoat painting, parts nickel-plated

RedBox-...

Terminal box for zone 2, 22.

MKK-S

mounting bracket for EEx-e terminal boxes type RedBox-... direct on actuator

RedSwitch

2

 

external aux. switches, 2 x EPU, adjustable, for zone 2, 22

KB-S

clutch for damper shafts 

Æ

 10...20 mm and   10...16 mm.

HV-S

comfortable manual override for RedMax actuators size S

Adaptations

various adaptations for dampers/valves on request

BFH-S

Mounting holder for actuators at fire danger area

FireSafe

Sensor with manufacturer certificate in acc. with ATEX.

AR-12-xx

Reduction of square damper connection from 12 mm to 11, 10, 9, 8

Содержание RedMax-...-BF-CT

Страница 1: ...or 10 sec at 90 On off 3 pos 2 contacts 5 85 EEx i circuit SB 7 0 7 1 RedMax 15 BF 15 Nm 24 230VAC DC 3 15 30 60 120 sec at 90 3 or 10 sec at 90 On off 3 pos 2 contacts 5 85 EEx i circuit SB 7 0 7 1 RedMax VA Type as above but with stainless steel housing AISI 316 for aggressive ambient 12x12 shaft shaft manual override cable glands and hollow rivet nickel plated RedMax CT Type as above but with A...

Страница 2: ...on Axle of the actuator double squared 12 x 12 mm direct coupling 100 overload protected and 100 self locking up to 15 Nm Electrical connection cable 1 m diameter of wires 0 5 mm for connection inside hazardous areas an terminal box is required Diameter of cable Æ 9 6 mm Æ 6 2 mm Cable gland M16 x 1 5 standard cable and wire entries are integral part of explosions proof encapsulation tested acc to...

Страница 3: ...same like supply of the actuator on same fuse 5 8 9 10 85 11 1 2 3 PE heater 5 24 230 VAC DC FireSafe 4 Attention If you use this type of wiring the heater does not work in case of open contact a b EEx i intrinsic safe data If 3 sec mode is selected the self adju stment ofAngle of rotation must be started and operation mode of max 10 ED must be guaranteed Never use actuators in this mode without e...

Страница 4: ...rection of the spring return function by left right mounting In acc to the actuator type 5 different motor running times and 2 different spring return running times can be selscted on site The integral heater is for ambient temperatures down to 40 C C Working with 3 sec motor running time See extra information EL D 3 pos control mode See extra information EL E Spring return Spring return function ...

Страница 5: ...it length in m Factor 0 0714 drive specific factor Vmm m based on the electrical conductivity of electrolytic copper with a coefficient of 56m Wmm pannel length L m terminal box actuator line cross section A mm voltage Uv V Formula for max cable length L at cable cross section A L A l Uv 18V 0 0714 Formula of needed cable cross section A at a cable length of L A 0 0714 l L Uv 18V The EL data sheet...

Страница 6: ...ate actuator in the 3 sec mode without an outside load of min 3 Nm Engaging 1 wire On Off controlls in the 3 sec modus with spring return the ac tuator can only be operated with 1 On Off function per minute otherwise electronics will be liable to overheating Attention If you use this type of wiring the heater does not work in case of open contact Attention If you use this type of wiring the heater...

Страница 7: ...se function bridge 3 4 reverse input and output signals Selection of running time for spring return Standard wiring spring return in 10 Sek Additional wiring terminal 5 spring return in 3 Sek B A B A B A B A SB 5 0 SB 5 1 SB 5 3 SB 5 2 I Operation with 3 sec motor running time mode While operating the ExMax actuator in 3 sec mode following parameters have to be aligned 1 Maximum cyclic duration 10...

Страница 8: ...tor sits diagonally on the squared damper shaft l The actuators have an angle of rotation of 95 inclusive 5 pre tention While assembling the pre loading was not considered l Dismount actuator of the damper use the enclosed socket wrench to draw up approx 5 over the hand operated control device before remounting on the damper shaft Consider additional information ME of the assembly instructions 09 ...

Страница 9: ... inl radius of bend for the cable All ExMax and RedMax actuators are equipped with a 10 position switch a push button and a multicolor LED for calibration These control elements are to be found cable laterally behind the two middle sectioned dummy plugs For operation these must be removed The calibration can be achieved despide lining up tension at the actuator The explosion prevention is not impa...

Страница 10: ...with drill template on the damper or to a mounting bracket 2 Adjust drive shaft of the actuator with the socket wrench that the drive stands perpendicular to the damper before pluging actuator on to the damper shaft 3 Plug actuator onto damper shaft and fix diagonally with 2 screws 4 Remove the socket wrench 5 Pivot and tighten the remaining screws Note the drive shaft is selflockingly produced an...

Страница 11: ...ire dampers Mounting to a ball valve Mounting to a butterfly valve Fire damper Assembly It is to be considered that the actuators have a total angle of rotation of approx 95 in order to realize a pre tention on the damper Therefore thr actuator sits tilted on the damper shaft In order to prevent this and to assure pre tention to the damper the driving shaft has to be adjusted mechanically before c...

Страница 12: ...ssory to the actuator Mounting of terminal boxes type ExBox RedBox via mounting bracket type MKK S to the actuator accessory 1 Put the squared connection part to the actuator then mount ExSwitch RedSwitch and fix it with 4 screws 2 ExMax RedMax with mounted ExSwitch RedSwitch 4 x 1 Screw mounting bracket MKK S to the actuator A then terminal box to the mounting bracket B schrauben 2 x 2 x B A Moun...

Отзывы: