Power supply design

               Rated current in acc. with motor running time

Voltage

Current

3/7,5s

15s

30s

60s

120s

230 V 

I

rated

0,5 A

0,3 A

0,15 A

0,10 A

0,10 A

120 V 

I

rated

0,75 A

0,4 A

0,3 A

0,25 A

0,25 A

48 V 

I

rated

2,0 A

0,5 A

0,3 A

0,2 A

0,2 A

24 V 

I

rated

4,7 A

1,45 A

0,52 A

0,4 A

0,4 A

The design of the on-site supply, depends on the selected motor running time and selected

supply voltage. Accompanying values are "about values", since there can be construction

unit dispersions within electronics. The power consumption in the blocking  position is run

time independently with max. 20 W. The power consumption for the heater is approx. 16W.

The heading is running only if the motor is in idle position! The initial starting supply voltage

required  by  the  actuators  power  supply  unit  is  around  2,0  A  for  about  1  Sec.

(Please  consider  this  while  concepting  the  cross  section  ot  the  supply  line)

Dimensioning/Design of the supply line

On long distances between voltage supply and drive, voltage drops occur due to line

resistances. As a consequence with 24 VAC/DC the actuator receives a too low tension

and does not start. In order to prevent this, the cross section of the inlet line is to be

designed/dimensioned accordingly. The accompanying formula allows the calculation of

the necessary line cross section, perhabs provides the maximally permitted conduit length

utilizing  the existing line cross section. Alternatively the secondary voltage can be increased

by selecting a transformer. For calcualtion purposses, following characteristics are essential:

UV = supply voltage in [V]

A = line cross section in [mm²]

L = conduit length in [m]

Factor 0.0714 = drive-specific factor

[Vmm²/m] ( based on the electrical conductivity of electrolytic copper with a  coefficient of

56m/Wmm²)

pannel

length "L" [m]

terminal box

actuator

line cross section "A" [mm²]

voltage

"Uv" [V]

Formula for max. cable length "L" at cable

cross section "A"

L = A 

(Uv-18V) : 0,0714

Formula of needed cable cross section

"A" at a cable length of "L"

A = 0,0714 

L : (Uv-18V)

The "EL"-data sheet contains additional information for ExMax and

RedMax actuators of the size "S", for the optimization and simplification

in regard to planning, installation and initial startup. It provides

influences of external factors in reference to the safe initiation of

the actuators, as well as technical references and problem solutions

(error indication). With the error indication, functions can be examined

and  different  error/problems  can  be  adjusted  locally.

Example: A = 1,5 mm², Uv = 24 V

Lengthof cable L = 126 m

Example: L = 250 m, Uv = 30 V

Cross section of  A = 1,5 mm²

Example:

24 V power supply with wire diameter 1,5 mm² = 126 m

Uv [V]

Schischek GmbH 

Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax  ++49 (0)9101-908177, Email [email protected]

ExMax-.. and RedMax-.. extra information EL - size S

E X P L O S I O N P R O O F

u

Power supply design

u

Design of line cross section 24...48 VAC/DC

u

Wiring alternatives for on-off, 3-pos, BF actuators

u

Wiring alternatives for modulating actuators

u

Use at ambient temperatures down to -20°C / - 40°C ( )

u

Error indication - problem treatment/solution

Power input depending of supply voltage

Dimensioning  of the line cross section with 24 ....48 VAC/DC supply voltages

ExMax/RedMax - extra information EL

For additional mechanical data have a look at "extra information ME"

28
27
26
25
24
23
22
21
20

50       100          150          200         250          300          350         400 L[m]

1 mm²

1,5 mm²

2,5 mm²

4 mm²

www.schischek.com

Содержание RedMax-...-BF-CT

Страница 1: ...or 10 sec at 90 On off 3 pos 2 contacts 5 85 EEx i circuit SB 7 0 7 1 RedMax 15 BF 15 Nm 24 230VAC DC 3 15 30 60 120 sec at 90 3 or 10 sec at 90 On off 3 pos 2 contacts 5 85 EEx i circuit SB 7 0 7 1 RedMax VA Type as above but with stainless steel housing AISI 316 for aggressive ambient 12x12 shaft shaft manual override cable glands and hollow rivet nickel plated RedMax CT Type as above but with A...

Страница 2: ...on Axle of the actuator double squared 12 x 12 mm direct coupling 100 overload protected and 100 self locking up to 15 Nm Electrical connection cable 1 m diameter of wires 0 5 mm for connection inside hazardous areas an terminal box is required Diameter of cable Æ 9 6 mm Æ 6 2 mm Cable gland M16 x 1 5 standard cable and wire entries are integral part of explosions proof encapsulation tested acc to...

Страница 3: ...same like supply of the actuator on same fuse 5 8 9 10 85 11 1 2 3 PE heater 5 24 230 VAC DC FireSafe 4 Attention If you use this type of wiring the heater does not work in case of open contact a b EEx i intrinsic safe data If 3 sec mode is selected the self adju stment ofAngle of rotation must be started and operation mode of max 10 ED must be guaranteed Never use actuators in this mode without e...

Страница 4: ...rection of the spring return function by left right mounting In acc to the actuator type 5 different motor running times and 2 different spring return running times can be selscted on site The integral heater is for ambient temperatures down to 40 C C Working with 3 sec motor running time See extra information EL D 3 pos control mode See extra information EL E Spring return Spring return function ...

Страница 5: ...it length in m Factor 0 0714 drive specific factor Vmm m based on the electrical conductivity of electrolytic copper with a coefficient of 56m Wmm pannel length L m terminal box actuator line cross section A mm voltage Uv V Formula for max cable length L at cable cross section A L A l Uv 18V 0 0714 Formula of needed cable cross section A at a cable length of L A 0 0714 l L Uv 18V The EL data sheet...

Страница 6: ...ate actuator in the 3 sec mode without an outside load of min 3 Nm Engaging 1 wire On Off controlls in the 3 sec modus with spring return the ac tuator can only be operated with 1 On Off function per minute otherwise electronics will be liable to overheating Attention If you use this type of wiring the heater does not work in case of open contact Attention If you use this type of wiring the heater...

Страница 7: ...se function bridge 3 4 reverse input and output signals Selection of running time for spring return Standard wiring spring return in 10 Sek Additional wiring terminal 5 spring return in 3 Sek B A B A B A B A SB 5 0 SB 5 1 SB 5 3 SB 5 2 I Operation with 3 sec motor running time mode While operating the ExMax actuator in 3 sec mode following parameters have to be aligned 1 Maximum cyclic duration 10...

Страница 8: ...tor sits diagonally on the squared damper shaft l The actuators have an angle of rotation of 95 inclusive 5 pre tention While assembling the pre loading was not considered l Dismount actuator of the damper use the enclosed socket wrench to draw up approx 5 over the hand operated control device before remounting on the damper shaft Consider additional information ME of the assembly instructions 09 ...

Страница 9: ... inl radius of bend for the cable All ExMax and RedMax actuators are equipped with a 10 position switch a push button and a multicolor LED for calibration These control elements are to be found cable laterally behind the two middle sectioned dummy plugs For operation these must be removed The calibration can be achieved despide lining up tension at the actuator The explosion prevention is not impa...

Страница 10: ...with drill template on the damper or to a mounting bracket 2 Adjust drive shaft of the actuator with the socket wrench that the drive stands perpendicular to the damper before pluging actuator on to the damper shaft 3 Plug actuator onto damper shaft and fix diagonally with 2 screws 4 Remove the socket wrench 5 Pivot and tighten the remaining screws Note the drive shaft is selflockingly produced an...

Страница 11: ...ire dampers Mounting to a ball valve Mounting to a butterfly valve Fire damper Assembly It is to be considered that the actuators have a total angle of rotation of approx 95 in order to realize a pre tention on the damper Therefore thr actuator sits tilted on the damper shaft In order to prevent this and to assure pre tention to the damper the driving shaft has to be adjusted mechanically before c...

Страница 12: ...ssory to the actuator Mounting of terminal boxes type ExBox RedBox via mounting bracket type MKK S to the actuator accessory 1 Put the squared connection part to the actuator then mount ExSwitch RedSwitch and fix it with 4 screws 2 ExMax RedMax with mounted ExSwitch RedSwitch 4 x 1 Screw mounting bracket MKK S to the actuator A then terminal box to the mounting bracket B schrauben 2 x 2 x B A Moun...

Отзывы: