Schindler 3100/3300/6300
J 43402603 / 01
134/269
Copyright © 2017 INVENTIO AG
2063
TRIP LEARNING UPPER FLAG EDGE NOT SET
C1:The EC application missed to set the upper flag for a level.
A1:Redo learning trip
2064
TRIP LEARNING LOWER FLAG EDGE ALREADY SET
C1:The EC application tried to set the value for a lower flag that was
already set. This can only happen, if we do not allow overwriting of the
shaft image (for example, while traveling upwards, where no value
should have been set before).
A1:Redo learning trip
C2:Possible problems with shaft info circuit? (PHS, light barrier, magnet
switch)
C3:EMC disturbances?
2065
TRIP LEARNING LOWER FLAG EDGE NOT SET
C1:The EC application missed to set the lower flag for a level.
A1:Redo learning trip
C2:Problems with shaft info circuit? (PHS, light barrier, magnet switch)
C3:EMC disturbance?
2066
TRIP LEARNING INVALID DOOR ENTRANCE SIDE
C1:The EC application tried to set a door side that is not allowed (its not
the same as 'already set', an invalid value is the problem.).
A1:Redo learning trip
C2:Problems with shaft info circuit? (PHS, light barrier, magnet switch)
C3:EMC disturbance?
2067
TRIP LEARNING DOOR ENTRANCE SIDE NOT SET
C1:The EC application missed to set a door side for a level.
A1:Check flags, Check light barrier cable, Check encoder, Redo learning
trip
2068
TRIP LEARNING DOOR ENTRANCE SIDE ALREADY SET
C1:The EC application tried to set a door entrance side that has already
been set.
A1:Check flags, Check light barrier cable, Check encoder, Redo learning
trip
2069
TRIP LEARNING INVALID LOWER FLAG EDGE
C1:The EC application tried to set the height of a lower flag edge bigger
than the height of the upper flag.
A1:Check flags, Check light barrier cable, Check encoder, Redo learning
trip
2070
TRIP LEARNING INVALID UPPER FLAG EDGE
C1:The EC application tried to set the height of a lower flag edge smaller
than the height of the upper lower flag.
A1:Check flags, Check light barrier cable, Check encode, Redo learning
trip