Table 30 Requested fuse current rating for UL class J/L and for IEC class gG
Ecosine
ecosine
ecosine
ecosine
Fuse class
J/L
Fuse class
gG
All FN 3470
All FN 3471
All FN 3480
All FN
3481
Rated
current
A
Rated
cur-
rent A
FN3470-250-99
FN3471-250-99
FN3480-315-99
FN3481-315-99
600
630
FN3470-315-99
FN3471-315-99
FN3480-355-99
FN3481-355-99
800
800
FN3470-355-99
FN3471-355-99
FN3480-400-99
FN3481-400-99
800
FN3470-400-99
FN3471-400-99
FN3480-500-99
FN3481-500-99
800
FN3470-500-99
FN3471-500-99
FN3480-550-99
FN3481-550-99
1000
i
UL class J
ii
UL class L
Table 31 Requested fuse current rating for UL class J/L
Ecosine
ecosine
ecosine
ecosine
Fuse class
J/L
All FN 3482
All FN 3483
All FN 3472
All FN 3473
Rated cur-
rent A
FN3482-350-99
FN3483-350-99
FN3472-280-99
FN3473-280-99
400
FN3482-400-99
FN3483-400-99
FN3472-315-99
FN3473-315-99
FN3482-450-99
FN3483-450-99
FN3472-356-99
FN3473-356-99
FN3482-500-99
FN3483-500-99
FN3472-400-99
FN3473-400-99
800
FN3482-600-99
FN3483-600-99
FN3472-480-99
FN3473-480-99
i
UL class J
ii
UL class L