Schaffner Group
User and Installation Manual
Ecosine
max
43/66
4 Ecosine max harmonic filter schematics and working principle
The base module of FN 3471, FN3473, FN 3481 and FN 3483 series contains line choke, trap choke
and trap capacitor, which helps reduce THDi to 5% for motor drives with an 4% DC-link choke present.
Figure 15 Schematic of FN 3471, FN 3473, FN 3481 and FN 3483 filter series
The base module of FN 3470, FN3472, FN 3480 and FN 3482 series contains line choke, load choke,
trap choke and trap capacitor, which helps reduce THDi to 5% for motor drives without DC-link choke
present. The base module schematic is shown in Figure 16.
Figure 16 Schematic of FN 3470, FN3472, FN 3480 and FN 3482 filter series
General working principle of ecosine max filter base modules is shown in Figure 17.
Figure 17 Working principle of ecosine max passive harmonic filters (with load choke Lo and without)
There is either trap disconnect jumper module or trap disconnect switch module available for
FN 3470/FN 3471, FN 3472/FN 3473, FN 3480/FN 3481 and FN 3482/FN 3483 filters.