The Speed Calibration is available on page 2 of the ' Speed Settings ' pressing
When the system is running empty, this command will cause eNod4 to initiate belt speed calibration sequence.
An internal speed sensor pulses counter is restarting and the calibration procedure duration will depend of the current belt
speed, the “total belt length” and the “number of revolutions” to handle.
Important: Before initiated speed calibration procedure, user has to configure the following parameters:
•
Conveyor total Length
•
Number of revolutions
12.2.5
Batch dosing
Parameter
Possible Value
Description
Batch dosing Parameters
Batch dosing
Yes / No
Allows the dosing stop automatically when the accumulated weight
reaches the weight target less totalization inflight value.
Reset totalization at
cycle start
Yes / No
When this option is activated the totalization is cleared each time a new
cycle starts.
Auto Stop conveyor
at end of batch
Yes / No
When this option is activated the dosing cycle is stopped automatically
when the accumulated weight reaches the weight target less totalization
inflight value.
Weight target
0 – 9999999.9
The batch target in weight unit
Totalization inflight
-9999999.9 –
9999999.9
The batch target inflight value in weight unit.