Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units
│
Document 26
-859
E
NG07 │ 2015-06-04
3
Digital room controller units
3-11
Function
Description
Presence Sensor
The presence sensor can be used to change the operat
-
ing mode manually to Comfort or Standby/unused. The
operating mode is shown in the display. The person icon
outside the little house indicates non-use; if this icon is
flashing, the controller is in Standby mode. In Comfort
mode, the person icon moves into the house.
Fan control
The HeaVAC menu can be used to set the fan speed
manually. The room controller can only switch to the
desired step if this is allowed by the fan operating window.
See description of Config FBox or registers (reg. 63, 64).
Light control
The Light and Shade menu can be used to switch up to
four light groups on/off manually. First, the Light menu is
activated with the oval SET key. Then the group is select
-
ed and switched on/off with the arrow keys. See descrip
-
tion of Config FBox or registers (reg. 120).
Blind control
The Light and Shade menu can be used to move up to
four blind groups up/down manually. First, the Shade
menu is activated with the oval SET key. Then the group is
selected and the blinds are controlled with the arrow keys.
See description of Config FBox or registers (reg. 120).
Note
All analogue inputs on the room controller can be read by the S-Bus via a Room
FBox or via registers independently of the application.
The use of a digital room control unit must be indicated in the configuration.
See description of Config FBox or registers.