Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units
│
Document 26
-859
E
NG07 │ 2015-06-04
3
Digital room controller units
3-22
Function
Description
Number of light groups
The lighting is controlled by group commands. The as
-
signment of individual lights to groups is part of the room
controller configuration. This may differ according to the
communications interface, and is described in the relevant
section of this Manual.
The room control unit has no knowledge of the room con
-
troller configuration. It is therefore necessary to param
-
eterise the number of supported light groups in the room
control unit separately.
Press
and
keys together for at least 5 seconds.
On the display, the light symbol flashes and the number of
light groups currently configured is shown. The
and
keys can be used to select the value 2, 4 or 8.
Factory setting: 2
Number of blind groups
Light and shade are controlled by group commands. The
assignment of individual blinds to groups is part of the
room controller configuration. This may differ according
to the communications interface, and is described in the
relevant section of this Manual.
The room control unit has no knowledge of the room con
-
troller configuration. It is therefore necessary to param
-
eterise the number of supported blind groups in the room
control unit separately.
Press
and
keys together for at least 5 seconds.
On the display, the blind symbol flashes and the number of
blind groups currently configured is shown. The
and
keys can be used to select the value 2, 4 or 8.
Factory setting: 2
Error codes
In the error case will be displayed a code with the letter “E“ followed by a number.
Please contact your service organisation.
PCD7.L662 SV2.8
E1: Internal temperature sensor defect.