Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units
│
Document 26
-859
E
NG07 │ 2015-06-04
3
Digital room controller units
3-15
for over 20 seconds, parameter mode will be terminated and the current setting will
become active.
Function
Description
Battery test
The
key is used to run the integrated test function.
All the display symbols flash and the charge level of the
battery is displayed; ON stands for sufficient capacity, but
when OFF is displayed, the battery should be changed.
IR zone address
To match a room control unit uniquely to a room. To ac
-
tivate the zone address setting, the function keys
,
and
must be pressed together for at least 1 second.
The display then shows the currently
e range from 0…30.In the room controller, this is part of
the configuration.
Factory setting: 0
Temperature measurement
The integrated temperature sensor can be used to meas
-
ure the room temperature.
To activate parameterisation, the
,
,
and
keys should be pressed together. The temperature symbol
on the display will then flash and the current setting will be
displayed. With the key
the mode has to be adjusted.
OFF: Temperature measurement disabledIf the room con
-
troller uses the temperature measurement from the room
control unit, the current room temperature in the room
controller will become invalid (99.9°C). See room control
-
ler configuration.
ON: Temperature measurement is enabled. The room
temperature will be transmitted after any 0.2°C change or
after 15 minutes without any change.ON with temperature
display: Temperature measurement is enabled and the
current room temperature will be permanently shown on
the display.
Factory setting: OFF