Saia-Burgess Controls AG
H
ardware manual for PCD3 series │ Document 26-789 ENG19│ 2018-06-29
Connections of the RIO head station PCD3.T76x for 4 modules
RIO (Remote Input Output) head stations
4-5
4
Profibus address
LSB
MSB
1 2 3 4 5 6 7 8
O
N
760
Saia PCD3.T
The Profibus address is set to binary on the PCD3.T76x
by means of a DIP switch.
The numbers on the DIP switch are assigned the
following values :
Valence
1
2
4
8
16
32
64
Unused
|
|
|
|
|
|
|
|
No. 1
2
3
4
5
6
7
8
Example for address 73:
DIP switch no. 1 + 4 + 7 on ON.
Expansion connection
760
Saia PCD3.T
This connector can be used to add up to 3 LIO module
carriers to the RIO (with PCD3.K010 connector). This
way, 256 I/Os can be realized per RIO.
4.3.2
Power LED
Supply
760
Saia PCD3.T
●
= LED on = supply available, OK