Saia-Burgess Controls AG
Hardware manual for PCD3 series │ Document 26-789 ENG19│ 2018-06-29
Addressing
Guidance
2-11
2
100
Saia PCD3.C
100
Saia PCD3.C
200
Saia PCD3.C
6860
ETH 2.1
ETH 2.2
Ethernet 2
USB
Saia PCD3.M
100
Saia PCD3.C
100
Saia PCD3.C
Extension cable
PCD3.K106
further series up to max. Address 1023
0
176
16
128
64
32
48
192
368
The address of the first module in a second or third series is determined by the
address of the last module in the previous 16.
For easier wiring, the module slots of the PCD3 module carriers are labeled with
the numbers 0 to 3. For more precise addressing, each module carrier and also
each module additionally has an address field in the lower right corner of the
housing. How these address fields are used is described
in the next chapter
.
Address 255 is reserved for the watchdog relay. Modules using this address must
not be inserted in module slot 16. For additional details, please see
Each additional module carrier PCD3.C100 / C200 offers space for 4 additional
I/O modules, at the end of the bus a PCD3.C110 provides space for 2 additional
I/O modules. The connection to the next series is made via the 26-wire extension
cable PCD3.K106 / K116.
Forces that occur at too small radii of the cable (smaller than the natural radius,
so buckling), can cause damage to the connector!
The extension cables must not be connected or disconnected while the
controller is under voltage!