SAUTER flexotron®400 - RDT410
Configuration
P100012103
34
Menu OK
Last of the configuration level menus is the OK-menu. To leave the configuration
level, go to this menu and klick on the encoder knob.
On exit from the configuration level you will not be returned to the Basic level but
to the Time and Scheduler level.
There is also a time-out function that will automatically exit the configuration level
after 5 minutes of inaction.
10.1 Storage of settings
All configuration settings become valid as soon as they are entered by clicking
the encoder knob. They are however not written to the flash memory until you
exit the configuration level either via the OK menu or via the time-out function.
To exit the configuration level without saving the changes to flash memory, cut
the supply voltage when still in the configuration level. All values will be kept as
they were before you entered the configuration level.
10.2 Reset to factory setting
The RDT410 can be reset to factory settings by configuring Domestic hot water
control (mode 5) and setting the D-factor to 99. Go to the Basic Display. Then cut
the power supply. When power is reapplied all configuration and scheduler
settings will be reset to factory setting.