SAUTER flexotron®400 - RDT410
Installation and wiring
P100012103
10
Terminal
Designation Operation
-
LS
24 V~
RDT410F201 only
-
MM
-
LS
230 V~
RDT410F301 only
MM
1
DI2
Digital input
2
DI+
Reference for DI1 and DI2
3
DI1
Digital input
4
UI+
Reference for UI1
1
DI2
Digital input
2
DI+
Reference for DI1 and DI2
3
DI1
Digital input
4
UI+
Reference for UI1
5
UI1
Universal input Ni1000 or Digital
6
Reference for AI1
7
AI1
Ni1000 temp. Sensor input
8
Reference for AI2
9
AI2
Ni1000 temp. Sensor input
10
SPI
Input Ni1000 setpoint device
11
AO2
0...10 V= output
12
AO1
0...10 V= output
13
Reference for AO1 and AO2
14
DO2
Digital output
15
DO1
Digital output
16
GDO
Reference for DO1 and DO2
17
NC
DO3
Relay
230 V~
5 A
18
NO
19
COM
4.2.1
Supply voltage
RDT410F301: 230 V~ +10%, -15%, 50/60 Hz. 6 VA
RDT410F201: 24 V~ ±15%, 50/60 Hz. 6 VA
If the RDT410 (24V supply model only) and actuators connected to it share
transformer, it is essential that the same transformer-pole is used as reference
for all the equipment. Failure to do so will prevent the equipment from
functioning as intended and may also lead to damages.