SAUTER flexotron®400 - RDT410
Configuration
P100012103
33
Menus X.9
Maximum compensation, CMP (Control mode 2)
Supply air max limit (Control mode 3)
High temperature setpoint (Control mode 4)
For control mode 2. The maximum setpoint compensation value.
Compensation will start to be added to the setpoint value when the outdoor
temperature falls below the start point S.P entered in menu 2.8. The
compensation will increase linearily up to the maximum value CMP which is
reached when the outdoor temperature has fallen to -20°C.
For control mode 3 the supply air temperature can be minimum and maximum
limited. In this menu you set the maximum supply air temperature.
For control mode 4 you need to establish a relationship between outdoor
temperature and supply water temperature. This is set by the two setpoints SP
L
and SP
H
where SP
L
is the water temperature to be held at an outdoor
temperature of +20°C and SP
H
is the water temperature to be held at -20°C.
Intermediate values are calculated with linear interpolation. In this menu you set
SP
H
.
Menu X.E
In this meny, you set whether you want to use an external setpoint device or set
the setpoint via the display. External setpoint can be used for control modes 1-3
and control mode 4 when using a room sensor. This menu is only available for
controllers with revision number R20 or later.
Menu I/O
After the last configuration menus there is a menu where you can look at the
actual values of all the inputs and outputs.