SAUTER flexotron®400 - RDT410
Configuration
P100012103
31
0°C temperature boost
In control mode 4 an extra temperature boost can be added at 0°C outdoor
temperature. The boost recedes from the set value to 0 over ±3 degrees.
Supply temp
Outdoor temp
SP
H
SP
L
-20
0
+20
D-factor
Control mode 5, Domestic hot water temperature control is often a very difficult
application which calls for responsive control. The RDT410 therefore utilises PID-
control for this control mode. In this menu you set the D-factor (the derivative
factor).
Menus X.7
Universal input UI1 (Control modes 1, 2, 3)
Pump exercise (Control mode 4)
Periodic overheating (Control mode 5)
Input UI1
For control modes 1, 2 and 3 you can choose to configure the universal input UI1
as either an analogue input for a frost protection sensor on either output
(snowflake-symbol) in a water-heated system or as a digital input for a high
temperature limiting switch (sun-symbol) in an electric heater. It can also be set
to --, not active.
If set to frost protection sensor RDT410 will activate the frost protection function
and also shutdown mode, see chapter 5.
If set to high temperature limit switch, the fan will run for an extra 3 minutes after
the heating output has been turned off at shutdown.
Frost protection on AO1
Frost protection on AO2
High temp. limit switch
Not used