Page
26
of
45
6.4
Unoccupied
A temperature setpoint entered by the technician during the setup and commissioning of the
controller. This set-point is used when the system is unoccupied.
6.5
Damper Operation
Damper Movement is determined by comparing the actual airflow reading through the
differential pressure and airflow set- points. If the current room temperature is 2 degrees within the
temperature set-point, no damper action will be initiated. Once is over the 2-degree Deadband,
the damper position will be move and changes.
7
System Integration and Networking
7.1
System Integration and Networking
These topics in this section will cover the integrating the ASV305BF7XXXW VAV controllers into a
Building automation network. These are advanced reference topics and are recommended to
control for technicians and engineers.
ASV305BF7XXXW VAV controller can be installed as a standalone controller or they can be
connected to a BACnet MS/TP network environment. The topics in this section are reference
material for technicians or engineers who are planning, installing, commissioning, and setting up a
controller that is connected to a network.
In addition to the information in this section, you will also need the following information:
1.
Detailed plans and drawings for the building automation system.
2.
Information about the Lan including routers, switches, and network firewalls configuration.
3.
Sequences of operation for other BACnet Devices that will be monitoring or interacting with
our ASV305BF7XXXW VAV actuators.