BACNET
OBJECT
ID
BACNET OBJECT
NAME
DESCRIPTION
/
RANGE
UNIT
DEFAULT
VALUE
READ/
MODBUS
WRITE ID
NOTE
AV26
AV26
Not use
-
-
R
R26
AV27
AV27
Not use
PPM
-
R
R27
AV28
AV28
Not use
Pa
-
R
R28
AV29
Airflow display
unit select
0=LPS
0.1=CFM
0.2=CMH
-
0.2
RW R29
(HMI)
-
AV30
Alarm code
No define
-
-
RW R30
-
AV31
HMI pushbutton
lock level
0=No Lock 1=Temp
Lock 2=All Lock
-
0
RW R31
(HMI)
-
AV32
HMI backlight
0-100
-
0
RW R32
-
AV33
Cooling
setpoint
av34-av35
°C/ °F -
RW R33
(HMI)
-
AV34
Cooling
set
point high limit
av35-9999
°C/ °F 30
RW R34
(HMI)
-
AV35
Cooling
set
point low limit
0-av34
°C/ °F -
RW R35
(HMI)
-
AV36
set up/dow n
step
0.1/0.2/0.5/1
°C/ °F 0.5
R
R36
-
AV37
Heating
set
point
AV39-38
°C/ °F 20
RW R37
-
AV38
Heating
set
point high limit
AV39-9999
°C/ °F 30
RW R38
-
AV39
Heating
set
point low limit
0-AV39
°C/ °F 0
RW R39
-
AV40
HMI Version
-
-
-
R
R40
-
AV41
HMI Passw ord
0-199
-
10(HMI
100)
0
R41
(HMI)
Value
is
mulitply by 10
AV42
HMI
Temperature
sensor offset
-10~10(0.1)
°C/ °F 0
RW R42
(HMI)
-
AV43
HMI
Humidity
sensor offset
-30~30(1)
%RH
0
RW R43
(HMI)
For
EY-
RU305F7002W
H and EY-
RU305F7003W
AV44
AV44
Not use
RW R44
AV45
AV45
Not use
-
-
-
R45
-