Configuring the VAV Terminal Box Options
The Configuring VAV terminal box options set the ASV305BF7XXXW VAV controller for specific
mechanical installation and configuration for the VAV box. The box options include the following
functions:
1.
Set Primary K factor
2.
Set VAV inlet diameter
3.
Cool or heating mode
Once the following procedure is set, please select “Save” or else the controller will not
capture
the configuration.
NO.
PROCEDURE
DETAIL STEPS
SENSOR DISPLAY
1
Enter VAV box
configuration
1.
Use the arrow to
“
VAV
”. Press the
power
button to select it
VAV on screen
2
Set Primary K
factor
1.
Once you press the power button on the
“
VAV
”, you should enter “K factor”
2.
Adjustable using “up” and “down” button
from -0 to 1000 value
3.
Press power button to move on to the next
function
K factor
3
Set VAV inlet
diameter
1.
Adjustable using “up” and “down” button
from 0 to 400 value
2.
Press power button to move on to the next
function MM/inch of the VAV terminal box
to be select
VAV inlet diameter
4
Cool or heating
mode
1.
Adjustable using “up” and “down” button
from “cool” or “Heat”
2.
Press power button to move on to the next
function
Cooling or Heating
Mode