Page
25
of
45
5.4
EY-RU305F700XW Series Room Thermostats
The EY-RU305F700XW series thermostats are digital wall mount sensors that include room
temperature, a digital LCD display and 3 push- button interfaces for entering set-points and
configuring the controllers. If an EY-RU305F700XW series room thermostat is detected by our
ASV305BF7XXXW VAV controller, the controller will automatically map the room thermostats to its
object list. For more information about detailed listing for input and output of object list, please
see BACnet object list, page 30 onwards.
The EY-RU305F700XW series room thermostats come with 3 models:
1.
EY-RU305F7001W
–
LCD Room Unit for ASV305BF7XXXW with Temperature Sensors
2.
EY-RU305F7002W - LCD Room Unit for ASV305BF7XXXW with Temperature and Humidity
sensors
3.
EY-RU305F7003W - LCD Room Unit for ASV305BF7XXXW with Temperature, Humidity and
Carbon Dioxide senor
6
Room Set points
6.1
Room Set points
There are four temperature set-points each for heating and cooling for a total of 5 set-points.
1.
Active Set-point
2.
Occupied cooling
3.
Unoccupied cooling
4.
Occupied heating
5.
Unoccupied heating
6.2
Active Set Point
The active set-point is the current set-point set by the user. The active set-point is determined by
the following:
1.
If space is occupied, the controller will use the occupied mode set-point as the active set-
point
2.
If an EY-RU305F700XW or NEVR series is connected, the Active set-point will be set via the
temperature set-point of the thermostats. The range of adjustment is set b
3.
If space is unoccupied, the controller will use the unoccupied set-point.
6.3
Occupied
A temperature setpoint entered by the technician during the setup and commissioning of the
controller. This set-point is used when the controller is occupied which is determined by the
Building Management System, motion sensors or the off/on occupancy button of the Thermostats.
Содержание ASV3
Страница 1: ...Page 1 of 45 MANUAL SAUTER ASV3 ...
Страница 2: ...Page 2 of 45 ...