2.2.4
Communications to BACnet MS/TP
•
BACNET MS/TP RS-485, 9600-76800 BPS, 1200M
•
Removable terminal block
•
Wire size recommended 22
–
24 AWG
•
Dip Switches on end of line termination return
2.2.5
Air Flow Sensor Features
•
CMOSens® Technology
•
Configured as BACnet analog input object. Measuring Range up to ±500 Pa (±2 inH2O) Span
accuracy of 5%
•
Zero-point accuracy 0.1pa
•
Tube connections for 1/4-inch FR tubing
2.2.6
Memory
•
Programs and program parameters are stored in non-volatile memory.
•
Auto restart on power failure.
2.2.7
Certification
•
Federal Communications Commission (FCC)
•
CE Certified
•
BACnet Testing Laboratory (BTL) listed as an application specific controller (B-ASC)
2.2.8
Actuator Specifications
Dimension (mm)