6 Commissioning
Turn the mode selector to the WINTER
position.
The green operating indicator on the
control panel turns on: the boiler is
ready to operate.
Open the isolating valves located on
the pipes: they will be placed in the
direction of the fl ow.
Open the automatic bleeders of the
system.
Open the fi lling loop valve situated
under the boiler until you obtain a 1 bar
pressure on the indicator (cold).
Bleed each radiator to remove the air,
re-tighten bleed screws.
Leave the cap on the pump auto air
vent open.
Flush the domestic hot water system by
opening the hot water taps for several
minutes.
Make sure the display indicates a
system pressure of between 1 and 2
bars. Re-fi ll system as necessary.
Make sure the condense syphon works
properly. It ensures the seal only when
it’s fi lled with condense (or water).
•
•
•
•
•
•
•
•
•
7 Specific
adjustments
7.1 Pump
speed
1
2
3
4
Legend
1 Speed
III
2 Speed
II
3 Speed
I
4
Speed selector of pump
Turn the selector (4) to choose pump
speed I, II or III in relation to the output/
pressure curve (see next page).
•
Содержание Semia Condens F24 E