background image

LE Series Oil Boiler

1.   Based on oil having a heating value of 140,000 BTU/Gal.
2.   Based on 13.5% CO2, maximum No. 1 smoke, and 0.00 in. w.c. in breeching.
3.   Based on a piping and pick-up allowance of 1.15.
4.   LE-1 furnished with components required for both firing rates.
5.   As an ENERGY STAR partner, Burnham has determined that this product meets the ENERGY
STAR guidelines for energy efficiency.

MODEL

NUMBER

I=B=R

FIRING RATE

GPH

( 1)

DOE

HEATING CAPA CITY

MBH

( 2)

I=B=R

NET RATING

MBH

( 3)

AFUE%

( 2)

A PPROX.

SHIPPING WEIGHT

LBS.

LEDV-1

0.60

74

64

86.7

325

LEDV-2

1.00

117

102

83.0

LEDV-3

1.25

143

124

81.5

      LE-1 (4)

       0.60 (5)

  74

  64

86.7

325

1.00

117

102

83.0

LE-2

1.25

143

124

81.5