The ASD-200 multisensor detector can detect the early stages of fire development when 
there is some visible smoke and/or temperature rise. It is designed for operation within the 
ABAX 2 / ABAX two-way wireless system. This manual applies to the detector with firmware 
version 1.00, which is supported by: 

 ABAX 

2: 

– ACU-220 

ACU-280 controller, 

–  ARU-200 repeater.  

 ABAX: 

–  ACU-120 / ACU-270 controller (firmware version 5.04 or newer), 
–  ARU-100 repeater (firmware version 2.02 or newer), 
–  INTEGRA 128-WRL control panel (firmware version 1.19 or newer and firmware 

version of processor used to operate ABAX system 3.10 or newer). 

The detector is not a construction product as defined in Regulation (EU) No 305/2011 
of the European Parliament and of the Council of 9 March 2011. 

Features 

  Visible smoke sensor. 

  Detection of optical chamber fouling. 

 Heat 

sensor. 

 Built-in 

sounder. 

  Red LED for optical signaling. 

 Test 

feature. 

  Battery status control. 

  “ECO” option for longer battery life (ABAX 2 system only). 

  Encrypted two-way radio communication in the 868 MHz frequency band (AES standard 

for the ABAX 2 system). 

  Transmission channel diversity – 4 channels for automatic selection of the one that will 

enable transmission without interference with other signals in the 868 MHz frequency 
band (ABAX 2 system only). 

  Remote update of detector firmware (ABAX 2 system only). 

  Tamper protection against enclosure opening. 

Description 

Radio communication 

The detector connects to the controller / control panel at regular time intervals to provide 
information about its state (periodical communication). Additional communication takes place 
in the case of alarm (smoke / high temperature is sensed by the detector) or tamper (tamper 
switch has been opened) and after restore of alarm (smoke / high temperature is sensed no 
more by the detector) or tamper (tamper switch has been closed). 

Содержание ASD-200

Страница 1: ...ASD 200 Wireless smoke and heat detector Firmware version 1 00 asd 200_en 03 19 SATEL sp z o o ul Budowlanych 66 80 298 Gdańsk POLAND tel 48 58 320 94 00 www satel eu ...

Страница 2: ... the enclosure base SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and software Current information about the changes being introduced is available on our website Please visit us at http www satel eu Hereby SATEL sp z o o declares that the radio equipment type ASD 200 is in compliance with Directive 2014 53 EU The full te...

Страница 3: ...r fouling Heat sensor Built in sounder Red LED for optical signaling Test feature Battery status control ECO option for longer battery life ABAX 2 system only Encrypted two way radio communication in the 868 MHz frequency band AES standard for the ABAX 2 system Transmission channel diversity 4 channels for automatic selection of the one that will enable transmission without interference with other...

Страница 4: ...larm Air temperature rise velocity Lower limit of response time Upper limit of response time 1 C min 29 min 40 min 20 s 3 C min 7 min 13 s 13 min 40 s 5 C min 4 min 9 s 8 min 20 s 10 C min 1 min 4 min 20 s 20 C min 30 s 2 min 20 s 30 C min 20 s 1 min 40 s Table 1 Response time limits for the heat sensor Fire alarm signaling The alarm is indicated visually LED steady light and acoustically continuo...

Страница 5: ...2 system Detection of optical chamber soiling The detector is monitoring the state of the optical chamber Deposition of dust in it may lead to malfunctioning of the device When the optical chamber requires cleaning this state is indicated by the LED Battery status control When the battery voltage is lower than 2 75 V the detector indicates low battery 3 short flashes of LED and 3 short beeps every...

Страница 6: ...lobby etc kitchen basement basic location for detector installation additional location for detector installation 4 Installation The detector enclosure can not be closed without the battery inserted Do not install the battery if the sounder is disconnected There is a danger of battery explosion when using a different battery than recommended by the manufacturer or handling the battery improperly ...

Страница 7: ...e signal strength The ARF 200 tester makes it possible to check the radio signal strength at the place of future installation without having to put the detector there 8 Remove the detector cover 9 Use wall plugs anchors and screws to secure the enclosure base to the ceiling The wall plugs anchors delivered with the device are intended for concrete brick etc For other types of surface drywall styro...

Страница 8: ...side the thermistor and its leads Fig 10 7 Pull aside the mounting catch of the optical chamber Fig 11 and remove it Fig 12 8 Using a soft brush or compressed air clean the labyrinth in the cover as well as the base of the optical chamber paying attention to the recesses where LEDs are installed 9 Replace the cover of the optical chamber 10 Place the thermistor leads in the respective grooves ...

Страница 9: ...the battery must be replaced 1 Start the service mode in the control panel if the controller is connected to a SATEL alarm control panel 2 Turn the cover counter clockwise Fig 5 and remove it Fig 6 3 Remove the discharged battery 4 Install a new CR123A 3 V lithium battery 5 Replace the detector cover 6 Press the test reset button Fig 1 Fire alarm should be triggered 8 Specifications Operating freq...

Отзывы: