background image

SATEL ASD-200 

Test mode 

The test mode makes diagnostics of the detector easier, because the detector LED indicates 
periodical communication and alarm memory.

 

How to start and end the test mode is 

described in the ABAX 2 / ABAX controller manual / the INTEGRA 128-WRL control panel 
manual. 

The alarm memory is cleared after ending the test mode. 

LED 

LED indicates: 

  low battery – 3 short flashes every 30 seconds, 

  alarm – ON for 5 minutes.  

When the ABAX 2 / ABAX system is running in the test mode, the LED indicates additionally: 

  periodical communication – short flash (80 milliseconds), and when the chamber is soiled 

- 2 short flashes, 

  memory of alarm triggered by smoke sensor – flashing rapidly, 

  memory of alarm triggered by heat sensor – flashing slowly. 

Energy saving mode (ECO) 

If you want to prolong the battery life, you can enable in the detector the “ECO” option. When 
the “ECO” option is enabled, the periodical communication takes place every 3 minutes. Thus 
the battery life can be increased as much as fourfold. The option is only available in the 
ABAX 2 system.  

Detection of optical chamber soiling 

The detector is monitoring the state of the optical chamber. Deposition of dust in it may lead 
to malfunctioning of the device. When the optical chamber requires cleaning, this state is 
indicated by the LED. 

Battery status control 

When the battery voltage is lower than 2.75 V, the detector indicates low battery: 3 short 
flashes of LED and 3 short beeps every 30 seconds. The low battery info is sent during each 
transmission to the controller / control panel. 

Selecting a mounting location 

  The detector is designed for indoor installation. 

  The detector should be installed in location close to the building / apartment exit (e.g. in 

the hall, lobby etc. – Fig. 2 and Fig. 3). 

  In the typical home or office applications, the detector should be installed on the ceiling, 

as close as possible to the center of the room, at a distance of at least 0.5 meters from 
the walls or other objects (Fig. 4). 

  Do not install the detector in places with high concentration of dust and/or formation and 

condensation of water steam. 

  Do not install the detector near heaters, cookers, fans or air-conditioner outlets. 

  Do not install the detector in places where there is no unobstructed movement of air (e.g. 

in recesses, niches, etc.). 

Содержание ASD-200

Страница 1: ...ASD 200 Wireless smoke and heat detector Firmware version 1 00 asd 200_en 03 19 SATEL sp z o o ul Budowlanych 66 80 298 Gdańsk POLAND tel 48 58 320 94 00 www satel eu ...

Страница 2: ... the enclosure base SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and software Current information about the changes being introduced is available on our website Please visit us at http www satel eu Hereby SATEL sp z o o declares that the radio equipment type ASD 200 is in compliance with Directive 2014 53 EU The full te...

Страница 3: ...r fouling Heat sensor Built in sounder Red LED for optical signaling Test feature Battery status control ECO option for longer battery life ABAX 2 system only Encrypted two way radio communication in the 868 MHz frequency band AES standard for the ABAX 2 system Transmission channel diversity 4 channels for automatic selection of the one that will enable transmission without interference with other...

Страница 4: ...larm Air temperature rise velocity Lower limit of response time Upper limit of response time 1 C min 29 min 40 min 20 s 3 C min 7 min 13 s 13 min 40 s 5 C min 4 min 9 s 8 min 20 s 10 C min 1 min 4 min 20 s 20 C min 30 s 2 min 20 s 30 C min 20 s 1 min 40 s Table 1 Response time limits for the heat sensor Fire alarm signaling The alarm is indicated visually LED steady light and acoustically continuo...

Страница 5: ...2 system Detection of optical chamber soiling The detector is monitoring the state of the optical chamber Deposition of dust in it may lead to malfunctioning of the device When the optical chamber requires cleaning this state is indicated by the LED Battery status control When the battery voltage is lower than 2 75 V the detector indicates low battery 3 short flashes of LED and 3 short beeps every...

Страница 6: ...lobby etc kitchen basement basic location for detector installation additional location for detector installation 4 Installation The detector enclosure can not be closed without the battery inserted Do not install the battery if the sounder is disconnected There is a danger of battery explosion when using a different battery than recommended by the manufacturer or handling the battery improperly ...

Страница 7: ...e signal strength The ARF 200 tester makes it possible to check the radio signal strength at the place of future installation without having to put the detector there 8 Remove the detector cover 9 Use wall plugs anchors and screws to secure the enclosure base to the ceiling The wall plugs anchors delivered with the device are intended for concrete brick etc For other types of surface drywall styro...

Страница 8: ...side the thermistor and its leads Fig 10 7 Pull aside the mounting catch of the optical chamber Fig 11 and remove it Fig 12 8 Using a soft brush or compressed air clean the labyrinth in the cover as well as the base of the optical chamber paying attention to the recesses where LEDs are installed 9 Replace the cover of the optical chamber 10 Place the thermistor leads in the respective grooves ...

Страница 9: ...the battery must be replaced 1 Start the service mode in the control panel if the controller is connected to a SATEL alarm control panel 2 Turn the cover counter clockwise Fig 5 and remove it Fig 6 3 Remove the discharged battery 4 Install a new CR123A 3 V lithium battery 5 Replace the detector cover 6 Press the test reset button Fig 1 Fire alarm should be triggered 8 Specifications Operating freq...

Отзывы: