When adding and removing the wireless devices, remember that the identification function
registers zones and outputs by groups of 8. Already after adding one wireless device which
takes up 1 zone, the control panel will reserve 8 zones in the system for wireless devices.
The LCD keypad makes it possible to select the zone to which that device will be assigned.
Observe continuity, i.e. avoid leaving any gaps in the list, which will later reduce the number
of available zones in the system. Remember to preserve continuity also when removing
wireless devices. For example, if the devices registered in the controller occupy 9 positions
on the list, then 16 zones (2x8) are reserved in the system. After removal of the device which
occupied position 7 on the list, there will still be 16 zones (2x8) reserved in the system for
wireless devices, although 8 positions are actually taken up on the list of wireless devices
(see: Table 2). In such a case, it is recommended that the last devices be removed from the
list and then added to the system again, so as to fill up the gap in the list and reduce the
number of zones reserved for wireless devices.
INTEGRA / INTEGRA Plus
ACU-270
zones
outputs
It..
list of devices
No
device
No
device
1
APD-100 detector
17 APD-100 detector
17 unused/unavailable
2
APD-100 detector
18 APD-100 detector
18 unused/unavailable
3
AMD-100 detector
19 AMD-100 detector
19 unused/unavailable
4
AMD-100 detector
20 AMD-100 detector
20 unused/unavailable
5
AMD-101 detector
21 AMD-101 detector
21 unused/unavailable
6 ^
22
AMD-101
detector
22
unused/unavailable
7
23
unused/unavailable 23
unused/unavailable
8 ASP-105
siren
8
24 ASP-105
siren
24 ASP-105
siren
9 ^
25 ASP-105
siren
25 ASP-105
siren
10 26
unused/unavailable 26
unused/unavailable
11 27
unused/unavailable 27
unused/unavailable
12 28
unused/unavailable 28
unused/unavailable
13 29
unused/unavailable 29
unused/unavailable
14 30
unused/unavailable 30
unused/unavailable
15 31
unused/unavailable 31
unused/unavailable
16
8
32 unused/unavailable 32
unused/unavailable
Table 2. An example of how the wireless devices should not be registered. For devices taking
up 8 positions, the system must reserve 16 zones and 16 outputs, as well as 2 addresses.
INTEGRA / INTEGRA Plus
ACU-270
zones
outputs
It.
list of devices
No
device
No
device
1
ASP-105 siren
17 ASP-105 siren
17 ASP-105 siren
2 ^
18 ASP-105
siren
18 ASP-105
siren
3
APD-100 detector
19 APD-100 detector
19 unused/unavailable
4
APD-100 detector
20 APD-100 detector
20 unused/unavailable
5
AMD-100 detector
21 AMD-100 detector
21 unused/unavailable
6
AMD-100 detector
22 AMD-100 detector
22 unused/unavailable
7
AMD-101 detector
23 AMD-101 detector
23 unused/unavailable
8 ^
8
24 AMD-101
detector
24 unused/unavailable
Table 3. An example of how to correctly register the wireless devices (compare also Fig. 5).
For 8 devices, the system has reserved 8 zones and 8 outputs, as well as 1 address.
In case of devices which, in addition to zones, also take up outputs, it is recommended that
you add them to the system first. This will allow you to maintain the continuity of use of not