80
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
63160-… Record
#1
(variable length)
...
Record
#16
(variable length)
Waveform Log Response Block
63152-63159
Block Heading
+0
Last file function
1, 3, 5, 11
UINT16
R
+1
File ID
17-18, 128 (F2)
UINT16
R
+2 Section
number
0-9
UINT16
R
+3
Section channel ID
F7
UINT16
R
+4
Number of records in the block
1
UINT16
R
+5
Record size, words
640
UINT16
R
+6 Request
variation
0
UINT16
R
+7 Reserved
0
UINT16
R
63160-63799
Waveform Log Record
+0
Record status
F5
INT16
R
+1
Record sequence number
0-65535
UINT16
R
+2, 3
Start time, seconds since 1/1/1970
F1
sec
UINT32
R
+4, 5
Start time, fractional seconds
µsec
UINT32
R
+6, 7
Trigger time, seconds since 1/1/1970
F1
sec
UINT32
R
+8, 9
Trigger time, fractional seconds
µsec
UINT32
R
+10
Record series number
1-65535
UINT16
R
+11
Record serial number in a series
0-65535
UINT16
R
+12
Trigger event type
F22
UINT16
R
+13
Trigger event number
1-65535
UINT16
R
+14
Source point ID (generic)
See Generic Data in Section 3.4
UINT16
R
+15
Trigger reference sample index
0–511
UINT16
R
+16
Sampling rate, µsec/sample
600-27000
×
0.1µsec UINT16 R
+17
Sampling rate, samples/cycle
32, 64, 128
UINT16
R
+18
Sampling frequency
4500 – 6500
×
0.01Hz
UINT16 R
+19
Channel offset, sampling units
0
INT16
R
+20, 21
Channel multiplier, primary units
See Generic Data in Section 3.4
UINT32
R
+22
Channel divisor, sampling units
32767
UINT16
R
+23
Length of a sample series, data points
512
UINT16
R
+24-127 Not
used
0
UINT16
R
+128
Sample Series
+128-639
Sample data series points [0...511]
-32768 - 32767
INT16
R
1
Power Quality (PQ) Log Response Block
63152-63159
Block Heading
+0
Last file function
1, 3, 5, 11
UINT16
R
+1 File
ID
26
UINT16
R
+2 Section
number
0
UINT16
R
+3
Section channel ID
0
UINT16
R
+4
Number of records in the block
1-16
UINT16
R