50
Address Point
ID
Description
Options/Range
3
Units
3
Type R/W
Notes
0x7418 Frequency
0-10000
×
0.01Hz
UINT32
0x7419 V1
THD
0-9999
×
0.1%
UINT32
2
0x741A V2
THD
0-9999
×
0.1%
UINT32
2
0x741B V3
THD
0-9999
×
0.1%
UINT32
2
0x7421
V1 interharmonics THD
0-9999
×
0.1%
UINT32
2
0x7422
V2 interharmonics THD
0-9999
×
0.1%
UINT32
2
0x7423
V3 interharmonics THD
0-9999
×
0.1%
UINT32
2
0x2980 V1
Pst
0-10000
×
0.01
UINT32
2
0x2981 V2
Pst
0-10000
×
0.01
UINT32
2
0x2982 V3
Pst
0-10000
×
0.01
UINT32
2
0x2983 V1
Plt
0-10000
×
0.01
UINT32
2
0x2984 V2
Plt
0-10000
×
0.01
UINT32
2
0x2985 V3
Plt
0-10000
×
0.01
UINT32
2
NOTES:
1
When the 4LN3, 4LL3, 3LN3, 3LL3, 3BLN3 or 3BLL3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line.
2
When the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages.
3
For volts, amps, power and frequency scales and units, refer to Section 4 ”Data Scales and Units”.
4
Harmonic angles are referenced to the fundamental voltage harmonic H01 on phase L1.
5
On a 0.2-s interval.
6
On a 3-s interval.