67
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
+17
Multi Fragment Interval
50 to 500 ms (default 50 ms)
UINT16
R/W
+18-21
Reserved
Read as 65535
UINT16
R/W
+22,23
Time Sync Period
1 to 86400 seconds (default 86400
sec)
UINT32
R/W
+24
Voltage scale, volts secondary
60 to 828V (default 144V)
V
UINT16
R/W
+25
Current scale, amps secondary
100
×
0.1A
UINT16 R/W
51184-51189 Reserved
DNP Events Setup
51190-51445
+0,1 Threshold/Deadband
0 to 4.3
×
10
9
UINT32
R/W
A hysteresis for the point return
threshold is 0.05Hz for frequency
and 2% of the operating threshold
for other points
+2
DNP point number
DNP point number available for the
selected object
UINT16
R/W
+3
Event scan control field (bitmap)
Bits 0-1 - DNP Object:
0 = none, 1=AI, 2=BI, 3=BC
Bit 2 – Object change event scan:
0= event disabled, 1=enabled
Bits 5-6 - DNP event poll class:
0=Class 1, 1=Class 2, 2=Class 3
Bit 7 - Event log on an event:
0= disabled, 1=enabled
Bits 8-9 – Threshold/Deadband
relation:
0=Delta, 1= more than (over
threshold), 2=less than (under
threshold)
UINT16
R/W
If Event log is enabled, the source
of a DNP event will be recorded to
the device Event log file as a
general Setpoint #17.
51190-51193
DNP Event #1
51194-51197
DNP Event #2
…
51442-51445
DNP Event #64
51446-51701 Reserved
DNP Class 0 Point Assignments
51702-51797
+0
DNP object and variation
F25
UINT16
R/W
+1
Start point number
Point number for the selected object
UINT16
R/W
+2
Number of points in a range
0-128
UINT16
R/W
51702-51704
DNP Class 0 Points Range 1
51705-51707
DNP Class 0 Points Range 2