61
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
+4
Volt/ampere/harmonic demand period
0 to 1800
sec
UINT16
R/W
+5-7 Reserved
UINT16
R
Read
as
65535
+8
Number of blocks in a sliding window
1 to 15
UINT16
R/W
+9-10 Reserved
UINT16
R
Read
as
65535
+11
Nominal line frequency
50, 60
Hz
UINT16
R/W
+12
Maximum demand load current
0 to 50,000 (0 = CT primary
current)
A UINT16
R/W
+13-17 Reserved
UINT16
R
Read
as
65535
+18
Nominal secondary voltage
10 to 690 V
UINT16
R/W
+19 Reserved
UINT16
R
Read
as
65535
+20
PT ratio multiplication factor
×
1,
×
10
UINT16
R/W
Communication Ports Setup
2344-2359
+0
Communication protocol
COM1: 0=Modbus RTU, 1=Modbus
ASCII, 2=DNP3.0, 5=Profibus DP
COM2: 0=Modbus RTU, 1=Modbus
ASCII, 2=DNP3.0
UINT16
R/W
+1
Interface
COM1: 0=RS-232, 1=RS-422,
2=RS-485, 4=Dial-up Modem,
6=Ethernet, 7=Profibus,
8=GSM/GPRS
COM2: 1=RS-422, 2=RS-485
UINT16
R/W
+2
Device address
Modbus: 1-247
DNP3.0: 0–65532
Profibus DP: 0-126
UINT16
R/W
+3
Baud rate
1=300 bps, 2=600 bps, 3=1200
bps, 4=2400 bps, 5=4800 bps,
6=9600 bps, 7=19200 bps,
8=38400 bps, 9=57600 bps,
10=115200 bps
UINT16
R/W
+4
Data format
0=7 bits/even parity,
1=8 bits/no parity,
2=8 bits/even parity
UINT16
R/W
+5
Flow control
0=no flow control
1=software (XON/XOFF)
2=hardware (CTS)
UINT16
R/W
N/A for COM2 (read as 65535)
+6
RTS mode
0=not used,
1=RTS is permanently asserted
2=RTS is asserted during the
transmission
UINT16
R/W
N/A for COM2 (read as 65535)
2344-2351
COM1 Setup
2352-2359
COM2 Setup
Device Options Setup
2376-2386