![Satec PM174 Series Скачать руководство пользователя страница 69](http://html1.mh-extra.com/html/satec/pm174-series/pm174-series_reference-manual_1200385069.webp)
69
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
Fault Log Recording Setup
52278-52341
V24.3.1 and higher
+0
Log options, bitmap
Bit 0 – waveform log on event start:
0 = disabled, 1 = enabled;
Bit 1 – waveform log on event end:
0 = disabled, 1 = enabled;
Bit 2 – recording to PQ log:
1 = disabled
UINT16
R/W
+1
Waveform log number
0-1 = log #1-#2
UINT16
R/W
+2
Data/RMS plot option
0 (N/A)
UINT16
R
+3
Data log number (factory preset) 0
(N/A)
UINT16
R
+4
1/2-cycle RMS plot, cycles before event
0 (N/A)
cycle
UINT16
R
+5
1/2-cycle RMS plot, cycles after event
0 (N/A)
cycle
UINT16
R
+6
1/2-cycle RMS plot duration, cycles
0 (N/A)
cycle
UINT16
R
+7-63 Reserved
UINT16
R
File Setup
52598-53877
+0 File
type
0
UINT16
R/W
+1
File attributes (bitmap)
F3
UINT16
R/W
+2
Number of records in the file
0-65535 (0 = delete file)
UINT16
R/W
+3
Number of sections/channels in the file
0-32
UINT16
R/W
0 = non-partitioned file
+4
Number of parameters per section record
1-16
UINT16
R/W
+5 Not
used
0
UINT16
R/W
+6
Section record size, bytes (for info only)
UINT16
R
+7
File record size, bytes (for info only)
UINT16
R
+8, 9
Allocated file size, bytes (for info only)
UINT32
R
52598-52607
Event Log Setup
52608-52617
Data Log #1 Setup
52618-52627
Data Log #2 Setup
52628-52637
Data Log #3 Setup
52638-52647
Data Log #4 Setup
52648-52657
Data Log #5 Setup
52658-52667
Data Log #6 Setup
52668-52677
Data Log #7 Setup
52678-52687
Data Log #8 Setup
52688-52697
Data Log #9 Setup
52698-52707
Data Log #10 Setup
52708-52717
Data Log #11 Setup
52718-52727
Data Log #12 Setup
52728-52737
Data Log #13 Setup
52738-52747
Data Log #14 Setup
52748-52757
Data Log #15 Setup
52758-52767
Data Log #16 Setup