62
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
+0
Power calculation mode
0=using reactive power: S=f(P,Q),
1=using non-active power:
Q=f(S,P)
UINT16
R/W
+1
Energy roll value
0=1
×
10
4
, 1=1
×
10
5
, 2=1
×
10
6
,
3=1
×
10
7
, 4=1
×
10
8
, 5=1x10
9
UINT16
R/W
+2
Phase energy calculation mode
0=disabled, 1=enabled
UINT16
R/W
+3 Reserved
UINT16
R/W
Read
as
65535
+4
Analog expander output option
0=none
1=0-20 mA
2=4-20 mA
3=0-1 mA
4=
±
1 mA
UINT16
R/W
+5
Battery mode
0 = battery is OFF, 1 = battery is
ON
UINT16
R/W
+6-9 Reserved
UINT16
R/W
Read
as
65535
+10
Energy LED test mode
0=disabled, 1=Wh test, 2=varh test
UINT16
R/W
LED pulse rate is 10,000
pulses/kWh
Alarm/Event Setpoints Setup
352-1055
+0
Condition #1: Logical operator
0 = OR, 1 = AND
UINT16
R/W
+1
Condition #1: Trigger parameter ID
F12
UINT16
R/W
+2
Condition #1: Reserved
0
UINT16
R/W
+3
Condition #1: Reserved
0
UINT16
R/W
+4,5
Condition #1: Operate limit
See Section 3.3
UINT32
R/W
Scaled value
+6,7
Condition #1: Release limit
See Section 3.3
UINT32
R/W
Scaled value
+8
Condition #2: Logical operator
0 = OR, 1 = AND
UINT16
R/W
+9
Condition #2: Trigger parameter ID
F12
UINT16
R/W
+10
Condition #2: Reserved
0
UINT16
R/W
+11
Condition #2: Reserved
0
UINT16
R/W
+12,13
Condition #2: Operate limit
See Section 3.3
UINT32
R/W
Scaled value
+14,15
Condition #2: Release limit
See Section 3.3
UINT32
R/W
Scaled value
+16
Condition #3: Logical operator
0 = OR, 1 = AND
UINT16
R/W
+17
Condition #3: Trigger parameter ID
F12
UINT16
R/W
+18
Condition #3: Reserved
0
UINT16
R/W
+19
Condition #3: Reserved
0
UINT16
R/W
+20,21
Condition #3: Operate limit
See Section 3.3
UINT32
R/W
Scaled value
+22,23
Condition #3: Release limit
See Section 3.3
UINT32
R/W
Scaled value
+24
Condition #4: Logical operator
0 = OR, 1 = AND
UINT16
R/W
+25
Condition #4: Trigger parameter ID
F12
UINT16
R/W
+26
Condition #4: Reserved
0
UINT16
R/W
+27
Condition #4: Reserved
0
UINT16
R/W
+28,29
Condition #4: Operate limit
See Section 3.3
UINT32
R/W
Scaled value
+30,31
Condition #4: Release limit
See Section 3.3
UINT32
R/W
Scaled value