Chapter 5 Configuring the PM135
General Meter Setup
84
PM135 Powermeter Series
Setpoints
), or can be linked to general pulse counters to count incoming
pulses (see
Configuring Counters
). They can also be linked to the
Billing/TOU registers to count pulses from external wattmeters or gas and
water meters.
Using PAS
Select
General Setup
from the
Meter Setup
menu, and then click on the
Digital Inputs
tab.
Figure
5-8: General Setup Dialog Box – Digital Inputs Dialog Box
The available options are shown in Table 11.
Table 11: Digital Input Options
Parameter
Options
Default
Description
Pulse Input
Mode
PULSE MODE
KYZ MODE
PULSE
MODE
In pulse mode, either leading, or
trailing edge of the input pulse is
recognized as an event. In KYZ
mode, both leading and trailing
edges of the input pulse are
recognized as separate events.
Pulse Polarity NORMAL (N.O.),
INVERTING (N.C.)
NORMAL For the normal polarity, the open
to closed transition is considered
a pulse. For the inverting polarity,
the closed to open transition is
considered a pulse.
It has no meaning in KYZ mode
where both transitions are used.
Debounce
Time
1-100 ms
10 ms
The amount of time while the
state of the digital input should
not change to be recognized as a
new state. Too low debounce time
could produce multiple events on
the input change.
The debounce time is applied the same for all digital inputs. If you change
the debounce time for a digital input, the same debounce time is
automatically assigned to the others.