![Satec PM135E Скачать руководство пользователя страница 166](http://html.mh-extra.com/html/satec/pm135e/pm135e_installation-and-operation-manual_1200373166.webp)
Appendix G Device Diagnostic Codes
166
PM135 Powermeter Series
Appendix G
Device Diagnostic Codes
Table 28: Device Diagnostic Codes
Diagnostic
Display
Diagnostic
Message
Description
Reason
RAM/DATA fault
RAM/DATA Fault Memory/Data fault
Hardware failure
HW watchdog
reset
HW Watchdog
Reset
Hardware watchdog
reset
Hardware failure
CPU exception
CPU Exception
CPU exception
Hardware failure
Run-time error
Run-time Error
Run-time software
error
Hardware failure
SW watchdog
reset
SW Watchdog
Reset
Software watchdog
timeout
Hardware failure
Power down/Up
Power Down
Power Down/Up
Normal power-up sequence
External restart
Device Reset
Warm restart
External restart via
communications or by
firmware upgrade
Configuration
reset
Configuration
Reset
Configuration reset
Corrupted setup data has
been replaced with the
default configuration
RTC fault
RTC Fault
RTC fault
The clock time has been lost
EEPROM fault
EEPROM Fault
EEPROM fault
Hardware failure
See
Diagnostics Display
in Chapter 3 for more information on the PM135