Satec PM135E Скачать руководство пользователя страница 1

 

 
 

 

PM135 Powermeter Series 

PM135P/PM135E/PM135EH

 

 

 

Installation and Operation Manual 

 

 

 

BG0518 Rev. A3

 

Содержание PM135E

Страница 1: ...PM135 Powermeter Series PM135P PM135E PM135EH Installation and Operation Manual BG0518 Rev A3 ...

Страница 2: ...ributor WARNING Read the instructions in this manual before performing installation and take note of the following precautions Ensure that all incoming AC power and other power sources are turned OFF before performing any work on the instrument Protect the measurement AC Inputs voltage V1 V2 V3 with 2A external overcurrent protection device and the power supply source inputs with 5A external overc...

Страница 3: ...ded Read this manual thoroughly before connecting the device to the current carrying circuits During operation of the device hazardous voltages are present on input terminals Failure to observe precautions can result in serious or even fatal injury or damage to equipment This equipment does not require cleaning for proper operation All trademarks are property of their respective owners Copyright 2...

Страница 4: ...he input terminals Failure to observe precautions can result in serious or even fatal injury or damage to equipment For complete and accurate in depth instructions refer to the following chapters in this manual 1 Installing the PM135 Mounting the PM135 Unit To mount the PM135 1 Position the PM135 unit in the square or round cutout If two PM135 are positioned side by side take care of proper interv...

Страница 5: ...ough the meter CT core Observe the arrow that indicates the current direction 4 In case of a retrofit application where each external CT ends with two wires Pass one wire through the meter CT core Connect the wire to one of the meter termination screws Connect the second wire from the external CT to the termination screw 5 Connect the measured voltage inputs 6 Connect COM1 RS 485 communication por...

Страница 6: ...6 PM135 Powermeter Series Common Wiring Mode 4LL3 or 4Ln3 CT wiring ...

Страница 7: ...ule on the meter 2 Power the PM135 unit on Assembling a module To operate the PM135 1 Perform device diagnostics 2 Configure the device through the PM135 unit front panel display Module connector cover RS 485 Terminals Remove Module Connector cover before assembling module ...

Страница 8: ...onfigure the PAS communications settings 4 Upgrade the meter firmware if a new version is available 5 Set up the meter using the PAS application software 6 Configure your security settings through the meter security setup 7 Configure your communication protocol settings 8 Configure Billing TOU registers At this stage the PM135 should be ready for operation ...

Страница 9: ...onnection 23 Voltage Input connection 24 Current Input Connection 24 Wiring Diagrams 25 2 5 I O Connections 30 4DI 2DO Module 30 8 DI module 32 12DI 4RO Module 32 4AO Module Analog Outputs 34 TOU module RTC and 4 Digital Inputs 34 2 6 Communications Connections 36 COM1 RS 485 Connection 37 ETH module COM2 Ethernet Connection 37 PRO module COM2 PROFIBUS Connection 38 RS 232 422 485 module COM2 Conn...

Страница 10: ...er 68 Uploading Setups from the Meter 69 4 5 Authorization 69 Chapter 5 Configuring the PM135 71 5 1 Configuring Communications 71 Setting Up Serial Communication Ports 71 Setting Up Ethernet 73 Setting Up GPRS Network 74 Setting Up eXpertPower Client 76 Setting Up TCP Notification Client 77 5 2 General Meter Setup 79 Basic Meter Setup 79 Transformer Correction 81 Device Options 82 Configuring Dig...

Страница 11: ...loading Files on Demand 129 8 2 Using the Upload Scheduler 130 8 3 Viewing Files On line 132 8 4 Exporting Files 132 Exporting Files in COMTRADE and PQDIF Formats 132 Exporting Files in Excel Format 134 8 5 Archiving Files 134 Chapter 9 Viewing Files 136 9 1 Operations with Files 136 9 2 Viewing Options 136 Customizing Views 136 Working with Tables 137 Working with Graphic Windows 138 9 3 Viewing ...

Страница 12: ...onic analysis capabilities The PM135 units include A 3 5 Monochrome Graphic LCD display enabling easy reading of local meters and can be provided in different languages1 A standard RS 485 communication port and a second optional Ethernet PROFIBUS or RS 232 RS 422 RS 485 port These ports allow local and remote automatic meter readings and setup through the supplemental communication or user data ac...

Страница 13: ... waveform monitoring capability Simultaneous 6 channel one cycle waveform capture at a rate of 64 samples per cycle Programmable Logical Controller Embedded programmable controller 16 control setpoints programmable thresholds and delays Relay output control see Available Options 1 cycle response time Event and Data Recording PM135E and PM135EH Non volatile memory for long term event and data recor...

Страница 14: ... TCP server on events or periodically on a time basis with the Ethernet module or with the RS 232 module using an external GPRS modem see Setting Up TCP Notification Client Meter Security Password security for protecting meter setups and accumulated data from unauthorized changes Upgradeable Firmware Easy upgrading device firmware through a serial or Ethernet port Software Support PAS free meter c...

Страница 15: ...ions programmable pulse width direct remote relay control through communications 1 cycle update time Analog Output The PM135 analog output AO expansion module provides 4 optically isolated analog outputs with an internal power supply Options for 0 20mA 4 20mA 0 1mA and 1mA output 1 cycle update time Additional Communication Port COM2 A second COM2 communication port can be ordered as an expansion ...

Страница 16: ...tomization to be used in dark or non safe locations or in places that are hardly accessible for observation See Configuring the Display in Chapter 5 for more information 1 4 Measured Parameters Table1 MeasuredandDisplayedParameters Parameter Display Comm Analog Pulse Alarm 1 cycle Real time Measurements RMS Voltage per phase RMS Current per phase kW per phase kvar per phase kVA per phase Power Fac...

Страница 17: ...ar Maximum Demand Export kVA Maximum Demand Total Energy E EH Total kWh Import Export Total kvarh Import Export Total kvarh Net Total kVAh Energy per Phase E EH kWh Import per phase kvarh Import per phase kVAh per phase TOU Registers E EH 4 TOU energy registers kWh and kvarh import export kVAh 4 pulse sources 4 TOU maximum demand registers 8 tariffs 4 seasons x 4 types of day Harmonic Measurements...

Страница 18: ...ries Parameter Display Comm Analog Pulse Alarm Min Max Frequency Neutral current Phase Rotation Voltage and Current Phase Angles Day and Time Pulse Counters Digital Inputs optional Relay Outputs optional Remote Relay Control optional Alarm Triggers Setpoints Self diagnostics ...

Страница 19: ...ified in Technical Specifications in Appendix A Electrical requirements as specified in Technical Specifications in Appendix A See Technical Specifications in Appendix A for more details 2 2 Package Contents The PM135 Powermeter package contains the following items PM135 Powermeter unit Technical Documentation CD Optional accessories depending on the options ordered if any Cables 2 3 Mechanical In...

Страница 20: ...meter in cutout ANSI 4 round or DIN 92x92mm square cutout 1 Position the meter in the cutout 2 Affix the meter using washers and nuts Add short text on Panel Mounting a heading should always have text Figure 2 2 Mounting DIN Rail Mounting The PM135 can be mounted on a 35 mm DIN rail Figure 2 3 Dimensions ...

Страница 21: ... Chapter 2 Installation Electrical Installation PM135 Powermeter Series 21 Figure 2 4 DIN Rail Mounting Figure 2 5 PM135 with 12DI 4RO module ...

Страница 22: ...uded in the building installation b It shall be in close proximity to the equipment and within easy reach of the OPERATOR c It shall be marked as the disconnecting device for the equipment Before installing ensure that all incoming power sources are shut OFF Failure to observe this practice can result in serious or even fatal injury and damage to equipment Typical Installation Figure 2 6 Typical I...

Страница 23: ... c It shall be marked as the disconnecting device for the equipment Before installing ensure that all incoming power sources are shut OFF Failure to observe this practice can result in serious or even fatal injury and damage to equipment The power source can be a dedicated fuse or a monitored voltage if it is within the instrument power supply range To connect an AC power supply 1 Connect the Line...

Страница 24: ...with direct connection Use any of the seven wiring configurations shown in Figures 2 8 through 2 15 120V Inputs Option U 120V inputs usually imply use of a potential transformer PT The PT requires use of any of the four wiring configurations shown in Figures 2 7 through 2 10 Current Input Connection The PM135 series provide two different CT connections Using internal CT the PM135 does not have cur...

Страница 25: ...e wiring configurations in the meter For more details see Basic Meter Setup in Chapter 5 Table2 WiringConfigurations Wiring Configuration Setup Code Figure 3 wire 2 element Delta direct connection using 2 CTs 3dir2 2 8 4 wire 3 element Wye direct connection using 3 CTs 4Ln3 or 4LL3 2 9 4 wire 3 element Wye connection using 3 PTs 3 CTs 4Ln3 or 4LL3 2 10 3 wire 2 element Open Delta connection using ...

Страница 26: ...on Electrical Installation 26 PM135 Powermeter Series Figure 2 9 3 Wire 2 Element Delta Direct Connection Using 2 CTs Wiring Mode 3dir2 Figure 2 10 4 Wire Wye 3 Element Direct Connection Using 3 CTs Wiring Mode 4LL3 or 4Ln3 ...

Страница 27: ... Electrical Installation PM135 Powermeter Series 27 Figure 2 11 4 Wire Wye 3 Element Connection Using 3 PTs 3 CTs Wiring Mode 4LL3 or 4Ln3 Figure 2 12 3 Wire 2 Element Open Delta Connection Using 2 PTs 2 CTs Wiring Mode 3OP2 ...

Страница 28: ...Series This configuration provides accurate power measurements only if the voltages are balanced Figure 2 13 4 Wire Wye 2 Element Connection Using 2 PTs 3 CTs Wiring Mode 3LL3 or 3Ln3 Figure 2 14 3 Wire 2 Element Open Delta Connection Using 2 PTs 3 CTs Wiring Mode 3OP3 ...

Страница 29: ...ical Installation PM135 Powermeter Series 29 Figure 2 15 4 Wire 3 Element Delta Direct Connection Using 3 CTs Wiring Mode 4LL3 or 4Ln3 Figure 2 16 3 Wire 2 Element Broken Delta Connection Using 2 PTs 3 CTs Wiring Mode 3bLn3 or 3bLL3 ...

Страница 30: ... OFF Failure to observe this practice can result in serious or even fatal injury and damage to equipment Figure 2 17 Module Connector Cover Before Module Assembly For I O ratings see Technical Specifications in Appendix A 4DI 2DO Module Figure 2 18 4DI 2DO Module Assembly Module connector cover RS 485 Terminals Remove Module Connector cover before assembling module ...

Страница 31: ...relay outputs provided for energy pulsing alarms or remote control Figure 2 19 Relay Output Connection Digital Inputs Four optically isolated status inputs are provided for status monitoring pulse counting external power demand period and time synchronization Figure 2 20 Digital Input Connection ...

Страница 32: ...put Connection 12DI 4RO Module The 12DI 4RO module can be equipped with optional communication port COM2 ETHERNET or RS 422 485 Figure 2 22 12DI 4RO Module Before I O Module installation ensure that all incoming power sources are shut OFF Failure to observe this practice can result in serious or even fatal injury and damage to equipment Relay Outputs There are four electro mechanic relay outputs p...

Страница 33: ...wermeter Series 33 Figure 2 23 Relay Output Connection Digital Inputs 12 optically isolated status inputs are provided for status monitoring pulse counting external power demand period and time synchronization Figure 2 24 12 Digital Input Connection ...

Страница 34: ... which has no live parts which are ACCESSIBLE The RATING of the insulation of the external equipment for use with the 4AO module shall comply according to Installation Category III for insulation to be suitable for SINGLE FAULT CONDITION The external equipment TERMINAL connection type is normally terminal block for wire size 14 AWG up to 1 5 mm2 The type of equipment that might be connected to the...

Страница 35: ...up replacement To replace the CR1632 RTC battery 1 Remove the TOU module from the PM135 compartment 2 Open the TOU MODULE case by applying a flat screwdriver at three snap in slit 1 2 and 3 as shown in Figure 2 27 3 Remove the old battery by lifting up the battery holder retractable tab 4 Place the new CR1632 battery into the battery holder while holding up the battery holder retractable tab in su...

Страница 36: ...ven fatal injury and damage to equipment Several communication options are available for the PM135 COM1 RS 485 COM2 on optional communication module Ethernet 10 100BaseT PROFIBUS DP GPRS RS 232 or RS 422 485 RF modem ISM frequency A connection to the Ethernet connector is made through a cable adaptor provided with your meter A full description of the communication protocols is found in the PM135 p...

Страница 37: ...35 Powermeter Series 37 port COM2 ETHERNET or RS 422 485 COM1 RS 485 Connection Figure 2 28 COM1 RS 485 2 Wire Connection The connector is removable with three captured wire terminals ETH module COM2 Ethernet Connection Figure 2 29 COM2 Ethernet Connection ...

Страница 38: ...ent that might be connected to the TERMINAL is Personal Computer PC or LAPTOP 10 100Base T LAN HUB and or Switch PRO module COM2 PROFIBUS Connection Figure 2 30 COM2 PROFIBUS Connection The PRO module TERMINAL is for use only with equipment which has no live parts which are ACCESSIBLE The RATING of the insulation of the external equipment for use with the PRO module shall comply according to Insta...

Страница 39: ... Installation Communications Connections PM135 Powermeter Series 39 RS 232 422 485 module COM2 Connection Figure 2 31 COM2 RS 232 connection Figure 2 32 COM2 RS 422 485 and 12DI 4RO RS 422 485 modules connection ...

Страница 40: ...WG 0 3mm The type of equipment that might be connected to the TERMINAL is Personal Computer PC or LAPTOP GPRS GSM modem module COM2 GPRS connection A GSM GPRS modem module can be connected to the meter COM2 port to provide communications with the remote MODBUS TCP server via a wireless GPRS network Figure 2 33 GSM GPRS modem Module The GSM GPRS SIM must not have any incoming voice call The custome...

Страница 41: ...with backlight for local data read outs meter setup and servicing The display operates in two modes Multi page data display mode with Auto Scroll feature allows you to scroll through display screens and pages to view various billing instrumentation and status data Programming mode allows you to enter menu driven device setups for inspecting and changing factory set meter parameters or resetting ma...

Страница 42: ...AB button function changes depending on the current display In display data mode monitoring pressing the TAB button moves from current data display to next data display For instance in Basic Setup selecting CT Primary Current A pressing the TAB button moves to next digit to be set The UP DOWN scroll buttons function changes depending on the current display In display menu mode pressing the UP DOWN...

Страница 43: ... The date order can be changed according to local rules via the Real Time Clock device setup menu Operating Mode Indicator The mode indicator gives information on the load presence and shows the direction of active power Indicator Icon Description Normal mode Test mode Tariff Rate Indicator The tariff rate indicator T1 through T8 shows the currently active tariff rate No Load Power Flow Direction ...

Страница 44: ...or is blinking If the phase voltage is either missing or below the voltage interruption threshold the phase indicator is replaced with a dash Display Features While energizing the device the display will show an init screen followed by phase voltages measurements as described below The PM135 display has a number of programmable features that can be disabled enabled and adjusted via the meter Displ...

Страница 45: ...solution for volts amps and powers presented on the front display and via communications See Device Options in Chapter 5 for information on selecting the data resolution in the PM135 Low Resolution Option Currents are displayed in whole amperes below 10 000 A and in kilo amperes above 10 000 A Measurement units for voltage and power depend on the voltage connection scheme For direct wiring PT 1 or...

Страница 46: ... factor and active power for the fundamental component 3 2 Data Displays The PM135 has 8 multi page data displays listed in the following table Data Display Menu Sequence Display Label Display Contents 1 Measurements Present 7 Measurements Data Displays V I P S Q PF Max DMD MIN MAX Energy and Billing TOU 2 Harmonics V I individual harmonics and Harmonics Spectrum 3 Waveforms Vn In Waveforms with T...

Страница 47: ...three active tariff rates The actual register contents in your installation may be different depending on your selection of register sources Each billing period display lists all total and tariff energy maximum demand and cumulative maximum demand registers for all configured billing registers and all active tariffs Use the UP DOWN button to scroll to the desired Billing TOU period register displa...

Страница 48: ... Active energy data Register 2 total readings Total Export Active energy data Register 2 tariff 1 readings Total Export Active energy data Register 2 tariff 2 readings Total Export Active energy data Register 2 tariff 3 readings Total Export Active energy data Register 3 total readings Total Import Reactive energy data ...

Страница 49: ...ve energy data Register 3 tariff 2 readings Total Import Reactive energy data Register 3 tariff 3 readings Total Import Reactive energy data Register 4 total readings Total Export Reactive energy data Register 4 tariff 1 readings Total Export Reactive energy data Register 4 tariff 2 readings Total Export Reactive energy data ...

Страница 50: ... for powers voltages currents and total harmonics Each quantity is displayed with the date and time of the last update Use the UP DOWN button to scroll to the desired Max DMD data display Import kW maximum demand Import inductive kvar maximum demand Import kVA maximum demand Export kW maximum demand Export inductive kvar maximum demand Export kVA maximum demand V1 V3 maximum demand Indicate V12 V3...

Страница 51: ... and inspecting the meter Use phase angles displays to check the order of phases when connecting wires to the meter terminals Use the UP DOWN button to scroll to the desired data display Phase to neutral voltages Only displayed in 4 wire configurations with a neutral Phase to phase voltages Phase to neutral voltages maximum demand with time stamp Phase voltage current angle Line frequency ...

Страница 52: ...Powermeter Series Voltage unbalance Phase voltage THD Indicate phase to phase voltage THD in line to line configurations Phase and neutral currents Phase and neutral currents maximum demand with time stamp Current unbalance Phase Current Total Demand Distorsion ...

Страница 53: ...ay Display Operations PM135 Powermeter Series 53 Phase Current THD Total powers and power factor Total powers maximum demand export Total powers maximum demand import Phase 1 powers and power factor Phase 2 powers and power factor ...

Страница 54: ...s voltages currents power factor and frequency Each quantity is displayed with the date and time of the last update Use the UP DOWN button to scroll to the desired Min Max data display Phase currents minimum maximum values with time stamp Neutral current minimum maximum values with time stamp Phase to neutral voltages minimum maximum values with time stamp Phase to phase voltages minimum maximum v...

Страница 55: ...otal power factor minimum maximum value with time stamp Line frequency minimum maximum value with time stamp Measurements Energy Data Display Energy displays show measurements total import export for energy and phases energy Use the UP DOWN button to scroll to the desired energy data display Total import energy Total export energy ...

Страница 56: ...s Display Harmonics display shows individual harmonics distortion for phase voltages and current and phase voltage current harmonic spectrum graphs Use the UP DOWN button to scroll to the specific harmonic number or voltage and current channels harmonic spectrum Individual harmonics phase voltages and currents Per phase current harmonic spectrum I1 I3 ...

Страница 57: ...s are given relatively to the V1 channel Three phase voltage and current Phasor diagram Digital I O The Digital I O display shows three sub menus Digital Inputs display to show status of each digital input Pulse Event Counters display to count external pulses or setpoint events or as time counters to count setpoint operation time Relay Outputs display to show status of each relay output Use the UP...

Страница 58: ...operation Device Control sub menu use the UP DOWN button to select whether Diagnostics or Alarms displays List of diagnostics messages List of alarms messages If there are diagnostic messages the diagnostic green led on the device panel flashes until you clear the device diagnostics Some of the diagnostics events are cleared automatically as the event source disappears See Device Diagnostic Codes ...

Страница 59: ...period number of blocks x block demand period and voltage and ampere demand periods Device Info Display The device info display provides different service information that may be required for meter identification and inspection like product module and firmware information I O module type communication settings and so on Use the UP DOWN button to scroll through the device info Meter identification ...

Страница 60: ...d Wh at a rate of 1 000 pulses per kWh TEST mode the LED pulses indicate either imported Wh or imported inductive varh at a rate of 10 000 pulses per kWh kvarh The energy test mode can be enabled through the Device Options setup When in test mode the energy and demand accumulators do not account for consumed energy Port Activity LEDs The meter has two green LEDs RX and TX which indicate activity o...

Страница 61: ...s setup COM1 Setup COM1 serial port setup Local Settings Local settings Setpoint Setup Password Setup Meter passwords setup Entering the Password The Setup Change menu can be secured by a four digit user password You can change the password and enable password protection through the Access Control menu see Configuring Meter Security The meter is primarily shipped with the password preset to 0 and ...

Страница 62: ... to the actual value to be changed Use the UP DOWN button to scroll through the desired value then press the SELECT ENTER button to store the selected value Note While being in the Device Setup operation mode the PM135 display will return to normal operation i e move to data display during idle operation of one minute Device Setup Reset Real Time Clock Display Setup Basic Setup Device Options COM1...

Страница 63: ... on your PC 1 Insert the installation CD supplied with your meter into CD drive 2 Open My Computer on your Desktop 3 Click on your CD drive icon select the PAS directory and then double click on Setup shown as an Application type file 4 Follow InstallShield Wizard instructions on the screen PAS is installed by default to the C Pas folder When installation is complete the PAS icon appears on your D...

Страница 64: ...te name for your device in the File name box click New and then click OK 5 On the Instrument Setup tab select PM135 in the Model box PAS automatically selects the appropriate instrument options for your meter 6 Select a correct CT secondary current 5A or 1A for your meter 7 If you wish to add any comments for your meter type the comments in the Comment box 4 3 Setting up Communications You can com...

Страница 65: ...communication protocol and port settings must match the settings you made in your meter Communicating through a Serial Port Select Serial Port Modem Site on the Configuration tab and then click on the Connection tab to configure your serial port settings Configuring a Serial Port 1 On the Connection tab select a COM port from the Device box and then click Configure Figure 4 2 Serial Port Setup Dia...

Страница 66: ...ase Break Timeout 5 In the Retries box define the number of attempts that PAS should use to receive a response from the meter in the event the communication fails before announcing a communication failure Communicating through the Internet If you are communicating through the Ethernet port define the IP address of your meter on the network To configure the meter IP address 1 On the Instrument Setu...

Страница 67: ...out the need to have it connected to your PC To prepare a setup for your meter 1 Select the device site from the list box on the PAS toolbar 2 Select the desired setup group from the Meter Setup menu Click on the tab with the setup you want to create or modify 3 Fill in the boxes with the desired configuration data for your meter 4 Click the Save as button to store the data to the meter site datab...

Страница 68: ...h to copy setups 2 Select Copy to from the Meter Setup menu 3 Select the target site database to which you wish to copy setups and click OK Downloading Setups to the Meter You can update each setup in your meter one at a time or download all setups together from the site database Individual Download To update a particular setup in your meter 1 Check the On line button on the PAS toolbar 2 Select a...

Страница 69: ...om the Meter Setup menu 3 Click on the tab of the setup you want to read from the meter As the dialog box opens PAS retrieves and displays the present setup data from the meter Click Receive if you wish to retrieve the meter setup once again 4 To store the setup to the meter site database click Save As and then click OK Batch Upload To upload all setups from the device to the site database at once...

Страница 70: ...owermeter Series Enter the password and click OK If your authorization was successful you are not prompted for the password again until you close the dialog box See Configuring Meter Security in Chapter 5 for more information on the meter password security ...

Страница 71: ...s Using the Front Display Select COM1 Setup or COM2 Setup from the Device Setup menu See Viewing and Changing Setup Options in Chapter 3 for information on configuring parameters via the front display Device Setup Reset Real Time Clock Display Setup Basic Setup Device Options COM1 Setup COM2 Setup See below for available communication options Using PAS Select Communications Setup from the Meter Se...

Страница 72: ... RS 485 COM2 232 RS 232 485 RS 485 422 RS 422 Eth Ethernet PRO PROFIBUS DP GPRS GPRS modem RS 485 Communication interface Not changeable on COM2 with the Ethernet and PROFIBUS modules Device address SATEC ASCII 0 99 MODBUS 1 247 DNP3 0 65532 PROFIBUS 0 126 1 126 for PROFIBUS Device network address Baud rate 300 bps 115 2 kbps 9600 bps The port baud rate Data format 7E 8N 8E 8N Data format and pari...

Страница 73: ...ome additional time until PAS restores a connection with your device Setting Up Ethernet Using the Front Display Select Network Setup from the Device Setup menu This menu entry appears only if the optional Ethernet module is plugged into the meter It allows you to set up the meter network address and the default gateway See Viewing and Changing Setup Options in Chapter 3 for information on configu...

Страница 74: ...port launches the second DNP3 TCP server allowing simultaneous connections on both TCP ports Selecting the MODBUS TCP port disables the DNP3 TCP server The TCP service port can also be changed trough the COM2 serial port setup Changing the communication protocol for the port automatically changes the TCP port for the Ethernet 3 When you change the device network settings through the Ethernet port ...

Страница 75: ...o set up the meter network address and the default gateway See Viewing and Changing Setup Options in Chapter 3 for information on configuring parameters via the front display Device Setup Reset Real Time Clock Display Setup Basic Setup Device Options COM1 Setup COM2 Setup COM2 Setup Protocol Interface Device Address Modbus RTU GPRS 1 Using PAS To set up GPRS communications 1 Select Communications ...

Страница 76: ...see Setting Up Serial Communication Ports 5 Configure your eXpertPower client see Setting Up eXpertPower Client or and TCP Notification client see Setting Up TCP Notification Client for communicating with a remote server You can check the status of the GPRS communications from the front panel via the Status Display or via the Device Control dialog in PAS see Viewing Communication Status and Statis...

Страница 77: ...operations of the eXpertPower client Time to Next Session min 1 99999 The time remaining to the next connection session NOTES 6 Do not enable the eXpertPower client in your meter if you do not use the eXpertPowerTM service 7 Do not change the connection time setting It is for information only The eXpertPower server updates it automatically Setting Up TCP Notification Client The TCP notification cl...

Страница 78: ...t 0 65535 502 The TCP service port of the notification server Message Exchange Address 0 65535 1000 The start address of a block of 16 MODBUS registers for receiving notification messages Connections with a remote server are triggered via programmable setpoints To send event notifications to a server configure a setpoint to respond to desired triggers or to periodic time events and put the Notific...

Страница 79: ...Description Basic Configuration Wiring Mode See Table 9 4Ln3 The wiring connection of the device PT Ratio 1 0 6500 0 1 0 The phase potential transformer s primary to secondary ratio PT Ratio Multiplier 1 10 1 PT Ratio multiplication factor Used in extra high voltage networks to accommodate the PT ratio for 500 kV and higher networks CT Primary Current 1 50000 A 5 A The primary rating of the phase ...

Страница 80: ...e wiring modes Table 9 WiringModes Wiring Mode Description 3OP2 3 wire Open Delta using 2 CTs 2 element 4LN3 4 wire Wye using 3 PTs 3 element line to neutral voltage readings 3DIR2 3 wire Delta Direct Connection using 2 CTs 2 element 4LL3 4 wire Wye using 3 PTs 3 element line to line voltage readings 3OP3 3 wire Open Delta using 3 CTs 2 element 3LN3 4 wire Wye using 2 PTs 2 element line to neutral...

Страница 81: ...marked ratio Angle V1 V3 V1 V3 transformer phase angle error minutes 600 to 600 0 The phase displacement in minutes between the primary and secondary values The phase angle of a voltage transformer is positive when the secondary value leads the primary value Ratio I1 I3 I1 I3 current transformer ratio correction factor 0 700 to 1 300 1 000 The ratio of the true transformer ratio to the marked rati...

Страница 82: ...ing reactive power S f P Q Nact using non active power Q f S P S f P Q The method used for calculating reactive and apparent powers see Power Calculation Modes below Energy Roll Value E EH 10000 kWh 100000 kWh 1000000 kWh 10000000 kWh 100000000 kWh 1000000000 kWh 10000000 The value at which energy counters roll over to zero Phase Energy Calculation E EH Disabled Enabled Disabled Enables phase ener...

Страница 83: ...reactive powers are measured directly and apparent power is calculated as 2 2 Q P S This mode is recommended for electrical networks with low harmonic distortion commonly with THD 5 for volts and THD 10 for currents In networks with high harmonics the second method is preferable When the non active power calculation mode is selected active power is measured directly apparent power is taken as prod...

Страница 84: ...e mode either leading or trailing edge of the input pulse is recognized as an event In KYZ mode both leading and trailing edges of the input pulse are recognized as separate events Pulse Polarity NORMAL N O INVERTING N C NORMAL For the normal polarity the open to closed transition is considered a pulse For the inverting polarity the closed to open transition is considered a pulse It has no meaning...

Страница 85: ...e alarm control setpoints in response to an event or by a remote command sent through communications It can also be linked to an internal pulse source to produce energy pulses Using PAS Select General Setup from the Meter Setup menu and then click on the Relay Outputs tab Figure 5 9 General Setup Dialog Box Relay Outputs Tab The available relay outputs options are shown in Table 12 Table12 RelayOu...

Страница 86: ...rgized in its non active state and is energized in its active operated state Inverting polarity the relay is normally energized in its non active state and is de energized in its active operated state It is called failsafe relay operation Pulse width 20 1000 ms 100 ms The actual pulse width is a multiple of the 1 cycle time rounded to the nearest bigger value The pause time between pulses is equal...

Страница 87: ...smitted through the analog output channel Zero scale Defines the low engineering scale in primary units for the analog output corresponding to a lowest zero output current 0 or 4 mA Full scale Defines the high engineering scale in primary units for the analog output corresponding to a highest output current 1 or 20 mA When you select an output parameter for the analog output channel the default en...

Страница 88: ...er automatically uses the full engineering scale setting for 1 mA with a negative sign Scaling Analog Outputs for 0 2 mA and 2 mA The 0 1mA and 1mA current outputs provide a 100 overload and actually output currents up to 2 mA and 2mA whenever the output value exceeds the engineering scale you set for the 1 mA or 1mA The output scales for 0 1 mA and 1 mA analog outputs are programmed for 0 mA and ...

Страница 89: ...ounter Value field 3 Click Send Configuring Alarm Control Setpoints The PM135 has an embedded logical controller that can perform different actions in response to user defined internal and external events Unlike a PLC the meter uses a simplified programming technique based on setpoints that allows the user to define a logical expression based on measured analog and digital values that produce a re...

Страница 90: ...tore your new setpoint settings after you configured all setpoint parameters 1 SELECT Save Setup function from Setpoint Setup menu and press SELECT ENTER button to enter Save Setup menu You are returned to the upper window and can select another setpoint or exit the menu 2 SELECT Save and press SELECT ENTER button to Save Setpoint parameters Using PAS Select General Setup from the Meter Setup menu...

Страница 91: ...ch trigger to provide hysteresis dead band for setpoint operations The Operate Limit defines the operating threshold and the second Release Limit defines the release threshold for the trigger The trigger thresholds are specified in primary units If you do not want to use hysteresis for the trigger set the Release Limit to the same value as the Operate Limit Using Binary Triggers Binary digital tri...

Страница 92: ...a the display A programmable action is performed on setpoint status transition when a setpoint event is asserted Generally setpoint actions are performed independently for each setpoint and can be repeated a number of times for the same target The exceptions are relay operations that are shared for each target relay between all setpoints using an OR scheme A relay output is operated when one of th...

Страница 93: ...auto scroll Auto Return Auto Return to Data Display screen diS disabled En Enabled Enabled Enables automatic return to the main display if no buttons are pressed for 5 minutes Backlight Display Backlight Continuous 1 10 min 1 Defines the backlight duration to be ON in idle operation Diagnostics LED Diagnostics indication LED Disabled Enabled Disabled Enables the diagnostic LED Phase Powers Phase P...

Страница 94: ...e that the On line button on the PAS toolbar is checked and then select RTC from the Monitor menu or click on the PAS toolbar Real Time Clock Button The RTC dialog box displays the current PC date and time and the time in your meter Figure 5 13 Real Time Clock Dialog Box Time and Date setup To synchronize the meter clock with the PC clock click Set Local Time Settings This setup allows you to spec...

Страница 95: ... Start Month DST Start Week of Month DST Start Weekday DST Start Hour March Last Friday 2 Local Settings DST Start Weekday DST Start Hour DST End Month Friday 2 September DST End Week of Month DST End Weekday DST End Hour Time Synchronization Input Last Sunday 2 None Using PAS Select General Setup from the Meter Setup menu and then click on the Local Settings tab Figure 5 14 General Setup Dialog B...

Страница 96: ...ternal port receiving the time synchronization pulses Daylight Saving Time When the daylight saving time is enabled the meter automatically advances the device clock by one hour when daylight saving time begins and puts the clock back one hour when it ends The default daylight saving time change points are preset for the U S A The daylight saving time option is disabled in the PM135 by default If ...

Страница 97: ...he display and communication ports To enable or disable password protection 1 Select Password Enabled field using the UP DOWN buttons 2 Press the ENTER button to enter the OFF ON Password Enabled display 3 Use the UP DOWN buttons to select the option ON enables password protection and OFF disables password protection 4 Press ENTER to confirm your new setting 5 Press ESC to exit the menu When passw...

Страница 98: ...e PAS toolbar is checked select Administration from the Monitor menu and then select Change Password Password 1 Figure 5 15 Password Setup Dialog Box To change the password 1 Type in a new 4 digit password 2 Repeat the password in the Confirm new password box 3 Check Enable password protection to enable password checking 4 Click Send ...

Страница 99: ...lling energy registers can be individually linked to the maximum demand register providing the same demand tariff structure as you selected for energy registers Recording Billing Data and Load Profiling The PM135E EH can provide automatic recording of the daily energy and maximum demand profile to a data log file Maximum demand profiling can be individually configured for every register See Factor...

Страница 100: ...egisters in a daily billing profile file both total and tariff registers if TOU is enabled Sum Profile Unchecked Checked Checked Enables recording total summary registers in a daily billing profile file Units kWh kvarh kVAh m3 CF cubic foot CCF hundred cubic feet None The register measurement units When a register is linked to an internal energy source it is set automatically When an external puls...

Страница 101: ...ach season To configure your daily profiles 1 Select the desired season and day type 2 Select the start time for each tariff change point and the corresponding active tariff number 3 Repeat the setup for all active profiles The first tariff change point is fixed at 00 00 hours and the last tariff change you specified will be in use until 00 00 hours on the next day NOTE The billing daily profile l...

Страница 102: ... multi season schedule on the start and end month for the selected season It does not matter which order of weekdays or months you select the meter recognizes the correct order 3 For exception days like weekends and designated holidays define a specific day either by a month and a month day or by selecting a month a week and a weekday within the month There are no limitations on how to build your ...

Страница 103: ... PM135 Configuring Billing TOU PM135 Powermeter Series 103 The above picture shows a typical single season tariff schedule with two daily tariff profiles configured for working days and weekends and the designated U S A holidays ...

Страница 104: ...om the Meter Setup menu and then click on the Log Memory tab Figure 5 19 Log Setup Dialog Box Log Memory Tab The following table describes file options Option Range Description Type Wrap around Non wrap Wrap around recording continues over the oldest records Non wrap recording is stopped until the file is cleared Size The size of memory allocated to the file Sections Channels 0 8 The numbers of se...

Страница 105: ...n configuring specific files see the following sections The following table can help you calculate an estimated file size when planning your memory allocation File Record Size Bytes File Size Bytes Event Log 16 Record size Number of records Conventional data Log 12 4 Number of parameters Record size Number of records Billing TOU daily profile log 12 4 Number of season tariffs 1 for the TOU summary...

Страница 106: ...ult the Event recorder stores all events related to configuration changes resets and device diagnostics Configuring the Data Recorder Conventional Data Log Files The Data recorder is programmable for recording up to 9 data parameters per record in each of the conventional data log files The list of parameters to be recorded to a data log is configurable individually for each file To create a new d...

Страница 107: ...Configure the list of parameters to be recorded in a log file You are not allowed to select more parameters than you defined when configuring your file Refer to Appendix D for a list of available parameters 3 For your convenience PAS follows your selection and helps you configure a series of the neighboring parameters when you open the Group box for the next parameter PAS highlights the same group...

Страница 108: ... the Data Log 16 partition with the left mouse button 3 Select the TOU Daily Profile file type 4 Select the number of season tariffs in your TOU schedule Add one additional parameter if you selected to record the Summary TOU total registers as well 5 Select the maximum number of records you want to be recorded in the file assuming that a new record will be added once a day 6 Click OK and send your...

Страница 109: ...TE INTERVAL trigger in Setpoint 1 see Configuring Alarm Control Setpoints Billing TOU Profile Data Log 16 Data log 16 is pre configured for daily billing energy and maximum demand recording for the last 90 days It is automatically updated once a day See Billing Profile Log File in Appendix E for the file record structure ...

Страница 110: ...ially these registers are reserved and none of them points to an actual data register To build your Modbus register map 1 Select Protocol Setup from the Meter Setup menu and click on the Modbus Registers tab 2 Click on the Default button to cause the assignable registers to reference the actual default meter register 6656 0 through 119 are not allowable register addresses for re mapping Figure 5 2...

Страница 111: ... Modbus Registers tab 2 Change the 32 bit register format in the Modbus Options pane 3 Click Send to download your setup to the meter Configuring DNP3 Refer to the PM135 DNP3 Reference guide for information on the DNP3 protocol implementation and a list of the available data points DNP Options Select Protocol Setup from the Meter Setup menu and click on the DNP Options tab Figure 5 22 Protocol Set...

Страница 112: ...it analog input readings to 16 bit object format otherwise it may cause an over range error if the full range value exceeds a 16 bit point limit Scaling is enabled by default It is not related to points that are read using 32 bit AI objects Refer to the PM135 DNP3 Reference Guide for information on the data point scales and a reverse conversion that should be applied to the received scaled values ...

Страница 113: ...object and variation type for a point range 3 Specify the start point index and the number of points in the range Refer to the PM135 DNP3 Reference Guide for available data points 4 Repeat these steps for all point ranges you want to be included into the Class 0 response 5 Click Send to download your setup to the meter The factory set Class 0 point ranges are shown in the picture below Figure 5 23...

Страница 114: ...lect the desired parameter to be cleared using the UP DOWN button then press the ENTER button 2 Press the ENTER button for approximately 5 sec until the Do notification is changed to Done Table 20 shows the reset options available from the front display Table 20 FrontDisplayResetOptions Display Label Description Volt Ampere Demands Clears ampere and volt maximum demands Power Demands Clears power ...

Страница 115: ...ies 115 Figure 6 1 Reset Dialog To reset the desired values or files 1 Click on the corresponding button and then confirm your command 2 If an entry has more than one target you are allowed to select targets to reset 3 Check the corresponding boxes and then click OK Figure 6 2 Reset Maximum Demands Dialog Box ...

Страница 116: ... view and clear device diagnostics from the front display Using PAS Ensure that the On line button on the PAS toolbar is checked select Device Control from the Monitor menu and then click on the Device Diagnostics tab See Device Diagnostic Codes in Appendix G for the list of diagnostic codes and their meaning Figure 6 3 Device Control Dialog Box Device Diagnostics Tab To clear the device diagnosti...

Страница 117: ...ts see Setting Up eXpertPower Client and Setting Up TCP Notification Client in Chapter 5 To clear the communication counters click on Clear You can also clear the communications counters via the PAS Reset dialog see Resetting Accumulators Maximum Values and Files 6 4 Remote Relay Control You can use PAS to send a remote command to your meter to operate any relay output or release a latched relay e...

Страница 118: ... Firmware can be downloaded via the Modbus RTU or Modbus TCP protocol through any communication port To download a new firmware file to your device 1 Ensure that the communication port you are connected through to the meter operates in Modbus mode 2 If you are connected to the meter through a serial interface it is recommended to set the port baud rate to 115 200 bps See Setting Up Serial Communic...

Страница 119: ... password and click OK If you did not change the password in the meter enter the default password 0 6 Observe the PM135 Display screen with Flash Loader Running notification as below 7 Wait until PAS completes upgrading your device It takes about 3 4 minutes at 115 200 bps to download the file to the meter 8 After upgrading firmware is completed the meter restarts so communications can be temporar...

Страница 120: ... Chapter 6 Device Control and Upgrading Upgrading Device Firmware 120 PM135 Powermeter Series lost You may need to wait a short duration until PAS restores a connection with your device ...

Страница 121: ... continuously Click on the Stop button to stop continuous polling The following picture shows a typical data monitor window Figure 7 1 RT Data Monitor Window You can open as many monitor windows as you wish either for different sites or for the same site using different data sets An open data monitor window is linked to the current site and does not change if you select another site in the site li...

Страница 122: ... single record or UnWrap to go to the multi record view Adjusting the Number of Rows in a Multi Record View Click the window with the right mouse button select Options adjust the number of records you want to see in the window and then click OK When the number of retrieved records exceeds the number of rows in the window the window scrolls up so that older records are erased See Working with Table...

Страница 123: ...tables and the number of records in each table you want recorded 5 Adjust the file update rate for automatic recording It must be a multiple of the sampling rate that you defined in the Instrument Setup dialog 6 Click Save When you run real time data polling PAS automatically saves retrieved records to a database at the rate you specified The RT Logging On Off button on the toolbar should be check...

Страница 124: ...C waveforms at a rate of 64 samples per cycle To give you a more representative picture PAS extends the waveforms across the window up to eight cycles by repeating the captured waveforms To select the channels you want to view click with the right mouse button on the waveform window select Channels check the channels for the phase you want displayed and then click OK See Working with Graphic Windo...

Страница 125: ...k on the waveform window with the right mouse button select Options click on the Phasor tab check the channel you want to make a reference channel and then click OK Viewing Symmetrical Components Waveform views have an additional pane at the right where PAS displays the symmetrical components for voltages and currents calculated for the point indicated by the left marker line To enable or disable ...

Страница 126: ...trieves harmonic spectrum for V1 V3 and I1 I3 channels Harmonics can be displayed as a spectrum chart for a selected channel or in a table PAS can also synthesize waveforms based on the harmonic spectrum to let you view a shape of the voltage and current waveforms in your network Viewing a Spectrum Chart Click on the button to view a spectrum chart for the selected channel To change a channel clic...

Страница 127: ...d selected compliance levels are colored in red on the graph and in the tables Figure 7 4 Harmonic Limits Viewing a Spectrum Table Click on the button on the local toolbar to display the harmonics spectrum in a tabular view for a selected phase or for all phases together The spectrum table shows voltage current active power and reactive power harmonic components both in percent of the fundamental ...

Страница 128: ...button on the local toolbar to view non overlapped voltage and current waveforms or click on the button to view them overlapped PAS shows a pair of 4 cycle voltage and current synthesized AC waveforms for a single phase To select the channels you want to view click with the right mouse button on the waveform window select Channels check the channels for the phase you want displayed and then click ...

Страница 129: ... store long term data profiles in one database regardless of the upload schedule you selected 8 1 Uploading Files on Demand To retrieve the log files from your meter 1 Ensure that the On line button on the PAS toolbar is checked 2 Select a device site from the list box on the PAS toolbar 3 Select Upload Logs from the Logs menu 4 Select a database or type the name for a new database and select a di...

Страница 130: ... from the Logs menu Figure 8 1 Upload Scheduler Setup Dialog Box 2 Click Add Site point to the site database for which you want to organize the schedule and then click OK 3 Click Browse and select a database for storing retrieved data or type the name for a new database select a directory where you want to save it and then click OK 4 Click Configure or double click on the site row ...

Страница 131: ...Enable box If your device is password protected by a communications password type in the password you set in the device to allow PAS to update the clock 8 Click on the Select Logs button check the boxes for logs you want to upload on a schedule and then click OK 9 Check the Enabled box at left to activate a schedule for the device 10 Click Close to store your schedule To keep the Upload Scheduler ...

Страница 132: ...ithout storing it to a file The data appears only in the window on your screen You can save it manually to the database To view the log data on line check the On line button on the PAS toolbar select the log you want to retrieve in the Logs menu and then click on the Poll button Only new log records are retrieved from the device If you want to review the entire log from the beginning click on the ...

Страница 133: ...ames are followed by a timestamp of the first event recorded to the file and may look like follows 12KVSUB_20040928T133038 pqd Automatic Converting PAS allows you to automatically convert data logs into PQDIF format at the time you upload data from your devices via the Upload Scheduler To automatically convert your data log tables into PQDIF format 1 Open the Upload Scheduler 2 Highlight a desired...

Страница 134: ...eter database see Creating a New Site for your Meter 8 5 Archiving Files Microsoft Access databases tend to grow fast Databases above 0 5 Gigabytes can drastically slow down file operations To avoid enormous growing files you can either periodically change the target database or use the Upload Scheduler s file archiver to automatically move older data to archives The Upload Scheduler archives file...

Страница 135: ... 8 Retrieving and Storing Files Archiving Files PM135 Powermeter Series 135 To avoid archiving partially updated data archiving is performed in a day after expiring a scheduled period and not before 2 hours a m ...

Страница 136: ...nd point to the file you wish to open 3 Select a desired table on the right pane and then click Open or double click on the table name Names of the last 16 files you opened are stored in the File menu so you can select them directly from the menu Saving Data to a File To save data from the open database table to a file 1 Click on the Save button and select a directory where you want your file to b...

Страница 137: ...3 Click OK Selecting Primary and Secondary Units Voltages and currents can be displayed in primary or secondary units To change units click on the table with the right mouse button select Options select the desired units for voltages and currents and then click OK Copying a Table To copy the entire table or its part into the Clipboard or into another application such as Microsoft Excel or Word 1 C...

Страница 138: ...waveform window with the right mouse button select Options click on the Axes tab select the desired units and then click OK Selecting Line Styles and Colors Channel waveforms can be displayed using different colors and line styles To change the colors or line styles click on the graph window with the right mouse button select Options click on the Display tab adjust colors and styles and then click...

Страница 139: ...ons on your local toolbar to zoom in and zoom out One click gives you a 100 percent horizontal or 50 percent vertical zoom Two buttons representing magnifying glasses give you a proportional zoom in both directions Copying a Graph To copy a graph or its part into the Clipboard or into another application such as Microsoft Excel or Word 1 Click on the graph window with the right mouse button and ch...

Страница 140: ...hat meet the criteria you specify Click on the Filter button or click on the report window with the right mouse button and select Filter Check the causes of events you want to display and then click OK PAS temporary hides rows you do not want displayed To change the default sorting order based on the date and time click on the Sort button or click on the report window with the right mouse button a...

Страница 141: ... view one data record per row or in a graphical view as a data trend graph Figure 9 2 Data Log Window Viewing Data Trend To view data in a graphical form click on the Data Trend button on the local toolbar To change the time range for your graph click on the Time Range button on the local toolbar and then select the desired date and time range ...

Страница 142: ...e enclosure plastic PC ABS blend Front panel plastic PC PCB FR4 UL94 V0 Terminals PBT UL94 V0 Connectors Plug in type Polyamide PA6 6 UL94 V0 Packaging case Carton and Stratocell Polyethylene Foam brackets Labels Polyester film UL94 V0 A 3 Power Supply 120 230 VAC DC Option Rated input 85 265VAC 50 60 400 Hz 88 290VDC Burden 9VA Isolation Input to ground 2500 VAC 12 VDC Option Rated input 9 5 18 V...

Страница 143: ...WG wire and 1 m long Overload withstand 15A RMS continuous 300A RMS for 1 second with 12AWG section wire 1A secondary option Operating range continuous 2A RMS Burden 0 02 VA In 1A with 12AWG wire and 1 m long Overload withstand 3A RMS continuous 80A RMS for 1 second with 12AWG section wire 40mA secondary External Solid or Split core CT option External CT Operating range continuous 10 100 1200A RMS...

Страница 144: ...ce 100 k Closed Input resistance 100 Galvanic isolation 3750 VAC 1 min Internal power supply 24VDC Scan time 1 ms Connector type removable 5 pins Wire size 14 AWG up to 1 5 mm2 A 7 Optional Analog Outputs 4 Analog Outputs optically isolated AO Optional module Ranges upon order 1 mA maximum load 5 k 100 overload 0 20 mA maximum load 510 4 20 mA maximum load 510 0 1 mA maximum load 5 k 100 overload ...

Страница 145: ... RS 232 422 485 Port RS 232 or RS 422 485 optically isolated port Isolation 3000 VAC 1 min Baud rate up to 115 2 kbps Supported protocols MODBUS RTU DNP3 and SATEC ASCII IEC 60870 5 101 Connector type removable 5 pins for RS 422 485 and DB9 for RS 232 Wire size up to 14 AWG up to 1 5 mm2 A 9 Real time Clock Standard Meter Clock Non backed clock Accuracy typical error 1 minute per month 25 C Typica...

Страница 146: ...magnetic RF Fields IEC 61000 4 4 level 3 Electric Fast Transient IEC 61000 4 5 level 3 Surge IEC 61000 4 6 level 3 Conducted Radio Frequency IEC 61000 4 8 Power Frequency Magnetic Field Meets ANSI IEEE C37 90 1 Fast Transient SWC Electromagnetic Emission Comply with IEC 61000 6 4 Radiated Conducted class A Comply with IEC CISPR 22 Radiated Conducted class A Safety Construction Meets IEC 61010 1 20...

Страница 147: ...o 70 Hz 15 Hz to 70 Hz 15 Hz to 70 Hz 320 Hz to 480 Hz Total Harmonic Distortion THD V I Vf If 999 9 1 5 0 2 THD 1 V 10 FSV and VL N 25V I 10 FSI 0 to 999 9 Total Demand Distortion TDD 100 1 5 TDD 1 I 10 FSI VL N 25V 0 to 100 Active energy Import Export Class 0 5S under conditions as per IEC 62053 22 2003 0 to 999 999 999 kWh Reactive energy Import Export Class 0 5S under conditions as per IEC 620...

Страница 148: ...ions 148 PM135 Powermeter Series 2 Specifications assume voltage and current waveforms with THD 5 for kvar kVA and PF and reference operating temperature 20 C 26 C 3 Measurement error is typically less than the maximum error indicated ...

Страница 149: ...var rt S kVA RT Total kVA rt PF PF RT Total PF r PF LG PF LAG RT Total PF Lag r PF Ld PF LEAD RT Total PF Lead 1 Cycle Auxiliary Values r nEU C In RT In Current rt Fr FREQ RT Frequency 1 Sec Phase Values Ar U1 V1 12 AVR 1 V1 V12 Voltage Ar U2 V2 23 AVR 1 V2 V23 Voltage Ar U3 V3 31 AVR 1 V3 V31 Voltage Ar U12 V12 AVR V12 Voltage Ar U23 V23 AVR V23 Voltage Ar U31 V31 AVR V31 Voltage Ar C1 I1 AVR I1 ...

Страница 150: ...n Description Acd q i kvar IMP ACD Accumulated kvar import demand Acd q E kvar EXP ACD Accumulated kvar export demand Acd S kVA ACD Accumulated kVA demand 1 In 4LN3 3LN3 and 3BLN3 wiring modes the voltages will be line to neutral for any other wiring mode they will be line to line voltages ...

Страница 151: ... 3 OFF Status input 3 OFF DI4 OFF STAT INP 4 OFF Status input 4 OFF DI5 OFF STAT INP 5 OFF Status input 5 OFF DI6 OFF STAT INP 6 OFF Status input 6 OFF DI7 OFF STAT INP 7 OFF Status input 7 OFF DI8 OFF STAT INP 8 OFF Status input 8 OFF DI9 OFF STAT INP 9 OFF Status input 9 OFF DI10 OFF STAT INP 10 OFF Status input 10 OFF DI11 OFF STAT INP 11 OFF Status input 11 OFF DI12 OFF STAT INP 12 OFF Status ...

Страница 152: ...HI kW EXP AVR High total kW export High kvar Imp Avr HI kvar IMP AVR High total kvar import High kvar Exp Avr HI kvar EXP AVR High total kvar export High kVA Avr HI kVA AVR High total kVA Low PF Lag Avr HI PF LAG AVR Low total PF Lag Low PF Lead Avr HI PF LEAD AVR Low total PF Lead 1 Sec Auxiliary Values High In Avr HI In AVR High neutral current High Freq Avr HI FREQ RT High frequency Low Freq Av...

Страница 153: ...rate relay RO2 Relay 3 ON OPERATE RELAY 3 Operate relay RO3 Relay 4 ON OPERATE RELAY 4 Operate relay RO4 Relay 1 OFF RELEASE RELAY 1 Release latched relay RO1 Relay 2 OFF RELEASE RELAY 2 Release latched relay RO2 Relay 3 OFF RELEASE RELAY 3 Release latched relay RO3 Relay 4 OFF RELEASE RELAY 4 Release latched relay RO4 Increment counter 1 INC CNT 1 Increment counter 1 Increment counter 2 INC CNT 2...

Страница 154: ...Status DI1 DI12 RELAYS Relays RO1 16 Relay Status RO1 RO4 COUNTERS Pulse Counters COUNTER 1 Counter 1 COUNTER 2 Counter 2 COUNTER 3 Counter 3 COUNTER 4 Counter 4 RT PHASE 1 Cycle Phase Values V1 V1 V12 Voltage 1 V2 V2 V23 Voltage 1 V3 V3 V31 Voltage 1 I1 I1 Current I2 I2 Current I3 I3 Current kW L1 kW L1 kW L2 kW L2 kW L3 kW L3 kvar L1 kvar L1 kvar L2 kvar L2 kvar L3 kvar L3 kVA L1 kVA L1 kVA L2 k...

Страница 155: ...L L voltage I AVG 3 phase average current RT AUX 1 Cycle Auxiliary Values In In neutral Current FREQ Frequency V UNB Voltage unbalance 2 I UNB Current unbalance 2 AVR PHASE 1 Second Phase Values V1 V1 V12 Voltage V2 V2 V23 Voltage V3 V3 V31 Voltage I1 I1 Current I2 I2 Current I3 I3 Current kW L1 kW L1 kW L2 kW L2 kW L3 kW L3 kvar L1 kvar L1 kvar L2 kvar L2 kvar L3 kvar L3 kVA L1 kVA L1 kVA L2 kVA ...

Страница 156: ...ary Values In In neutral Current FREQ Frequency V UNB Voltage unbalance 2 I UNB Current unbalance 2 PHASORS Phasors V1 Mag V1 V12 Voltage magnitude 1 V2 Mag V2 V23 Voltage magnitude 1 V3 Mag V3 V31 Voltage magnitude 1 I1 Mag I1 Current magnitude I2 Mag I2 Current magnitude I3 Mag I3 Current magnitude V1 Ang V1 V12 Voltage angle 1 V2 Ang V2 V23 Voltage angle 1 V3 Ang V3 V31 Voltage angle 1 I1 Ang I...

Страница 157: ...DMD Billing Summary Total Accumulated Demands E EH REG1 ACD Register 1 accumulated demand REG2 ACD Register 2 accumulated demand REG3 ACD Register 3 accumulated demand REG4 ACD Register 4 accumulated demand SUMM BLK DMD Billing Summary Total Block Demands E EH REG1 BD Register 1 block demand REG2 BD Register 2 block demand REG3 BD Register 3 block demand REG4 BD Register 4 block demand SUMM SW DMD...

Страница 158: ...stortions EH I1 HD01 H01 Harmonic distortion I1 HD02 H02 Harmonic distortion I1 HD40 H40 Harmonic distortion HD I2 I2 Harmonic Distortions EH I2 HD01 H01 Harmonic distortion I2 HD02 H02 Harmonic distortion I2 HD40 H40 Harmonic distortion HD I3 I3 Harmonic Distortions EH I3 HD01 H01 Harmonic distortion I3 HD02 H02 Harmonic distortion I3 HD40 H40 Harmonic distortion ANG V1 V1 V12 Harmonic Angles EH ...

Страница 159: ...rrent I2 H01 I2 Current I3 H01 I3 Current kW L1 H01 kW L1 kW L2 H01 kW L2 kW L3 H01 kW L3 kvar L1 H01 kvar L1 kvar L2 H01 kvar L2 kvar L3 H01 kvar L3 kVA L1 H01 kVA L1 kVA L2 H01 kVA L2 kVA L3 H01 kVA L3 PF L1 H01 Power factor L1 PF L2 H01 Power factor L2 PF L3 H01 Power factor L3 HRM TOT POW Fundamental and Harmonic Total Power Values kW H01 Total fundamental kW kvar H01 Total fundamental kvar kV...

Страница 160: ...I2 Maximum ampere demand I3 DMD MAX I3 Maximum ampere demand kW IMP SD MAX Maximum kW import sliding window demand kW EXP SD MAX Maximum kvar import sliding window demand kvar IMP SD MAX Maximum kW export sliding window demand kvar EXP SD MAX Maximum kvar export sliding window demand kVA SD MAX Maximum kVA sliding window demand In DMD MAX In neutral current maximum demand MAX SUMMARY DMD Billing S...

Страница 161: ... Tariff 1 maximum demand REG3 TRF2 MD Tariff 2 maximum demand REG3 TRF8 MD Tariff 8 maximum demand TOU MAX DMD REG4 Billing TOU Maximum Demand Register 4 E EH REG4 TRF1 MD Tariff 1 maximum demand REG4 TRF2 MD Tariff 2 maximum demand REG4 TRF8 MD Tariff 8 maximum demand 1 In 4LN3 3LN3 and 3BLN3 wiring modes the voltages will be line to neutral for any other wiring mode they will be line to line vol...

Страница 162: ...tal register accumulated demand REG1 BD SUM REG1 BLK DMD Billing summary total register block demand REG1 SD SUM REG1 SW DMD Billing summary total register sliding demand REG1 SUM REG1 Billing summary total energy register REG1 MD SUM REG1 DMD MAX Billing summary total register maximum demand REG1 TRF1 TOU REG1 TRF1 Billing tariff energy register REG1 TRF1 MD DMD1 TRF1 MAX Billing tariff register ...

Страница 163: ...ergy reading 3 TRF2 Tariff 2 energy reading 4 TRF3 Tariff 3 energy reading 5 TRF4 Tariff 4 energy reading 6 TRF5 Tariff 5 energy reading 7 TRF6 Tariff 6 energy reading 8 TRF7 Tariff 7 energy reading 9 TRF8 Tariff 8 energy reading Daily Maximum Demand Register 1 1 REG1 MD Summary total max demand reading 2 TRF1 MD Tariff 1 max demand reading 3 TRF2 MD Tariff 2 max demand reading 4 TRF3 MD Tariff 3 ...

Страница 164: ...x E Billing TOU Profile Log File 164 PM135 Powermeter Series The number of parameters in each section is automatically configured depending on the number of actual tariffs you defined in the TOU Daily Profiles ...

Страница 165: ...e scale PT Ratio V 1 Maximum current I max All configurations Current scale CT Ratio A 2 3 Maximum Power 4 Wiring 4LN3 3LN3 3BLN3 V max I max 3 W Wiring 4LL3 3LL3 3BLL3 3OP2 3OP3 3DIR2 V max I max 2 W Maximum frequency 25 50 or 60 Hz 100 Hz 400Hz 500 Hz 1 The default voltage scale is 144V The recommended voltage scale is 120V 20 144V for using with external PT s and 690V 20 828V for a direct conne...

Страница 166: ...n time software error Hardware failure SW watchdog reset SW Watchdog Reset Software watchdog timeout Hardware failure Power down Up Power Down Power Down Up Normal power up sequence External restart Device Reset Warm restart External restart via communications or by firmware upgrade Configuration reset Configuration Reset Configuration reset Corrupted setup data has been replaced with the default ...

Страница 167: ...3 74 75 76 147 Event recorder 108 eXpertPower 77 F factory defaults 107 G GPRS 14 16 41 73 76 77 119 H High Resolution Option 46 I inputs 18 L Low Resolution Option 46 M Maximum Demand Load Current 80 Modbus 112 N notification 78 O Open Delta 26 28 29 81 P PAS 64 password 62 71 Phase Energy 83 Power Source 24 Profibus 12 14 15 36 39 73 147 PT Ratio 80 167 Pulse LED 61 R Reactive energy 149 Reactiv...

Отзывы: