Hardware Configuration
PR 5610 Installation Manual
50 Sartorius
3.4.9 PR 1713/15 4 Opto inputs / 4 Relay outputs
Max. 3 cards PR 1713/15 can be used. The digital interfaces are passive
(external supply is necessary) and have no
common potential.
Connecting method:
2-row 25-pin connector
Terminal block A/B with 2x8
screw terminals
Number of inputs / outputs:
Inputs: 4 , outputs: 4
Input signal:
Low: 0 ... 5V or open
High: 10 ... 31 V
External supply required
Input current:
< 7 mA at 24 V
< 3 mA at 12 V
Output:
Max. switching voltage : 31 V DC
Max. switching current : 1 A DC
Output relay contact:
Closing (default, jumper pos. A)
Opening (change jumper to pos.
B)
See drawing
Potential isolation:
Yes, input: optocoupled
output: potential free contacts
Dimension (LxWxH):
80 x 68 x 15 mm
Weight:
50 grs.
Cable length (screened):
Max. 50 m
•
4x outputs, relay (low voltage current), not for explosion-hazarded area zone 2.
•
4x inputs, dig. (On -Off) IN for process control.
The input is galvanically isolated via optocoupler. The input signal of the digital interface is a logical "0" with
open input lines.
Accessories / options: external supply required
Pin allocation of option connectors in the unit (installation see chapter 3.2.1)
Terminal
block
B
input
B1 B2 B3 B4 B5 B6 B7 B8
upper row
4 channels
+ CH1 - CH1 + CH2 - CH2 + CH3 - CH3 + CH4 - CH4
Terminal block A
output relay
A1
A2
A3
A4
A5
A6
A7
A8
lower
row
4
channels CH1 CH1 CH2 CH2 CH3 CH3 CH4 CH4