2-2-2. Outdoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Type
Rotary (Hermetic)
Compressor model ... Number
C–1R71H5U ... 2 / 80688745 – S ... 2
Nominal output
W
700
Compressor oil ... Amount
cc
4GS D –T or SAY-56T ... 320
✕
2
Coil resistance (Ambient temp. 25°C)
Ω
C – R : 4.57
C – S : 6.90
Type
External protector (OLR 1, 3)
External protector (OLR 2, 4)
Safety
Overload relay ... Number
MRA98782 – 9201 ... 2
CS – 7C115 ... 2
devices
Operating temp.
Open
°C
130 ± 5
115 ± 3
Close
°C
69 ± 11
95 ± 5
Operating amp.(Ambient temp. 25°C)
Trip in 6 to 16 sec. at 13.5A
—
Run capacitor ... Number
µF
20.0 ... 2
VAC
400 ... 2
Type
Propeller
Number ... Dia.
mm
1 ... ø420
Fan motor model ... Number
KFG6 – 51C5P – S ... 1
No. of poles ... rpm (230 V)
6 ... 870
Nominal output
W
50
Coil resistance (Ambient temp. 20°C)
Ω
WHT – BRN : 67.1
WHT – YEL : 83.8
Safety
Type
Thermal protector
devices
Operating temp.
Open
°C
130 ± 8
Close
Automatic reclosing
Run capacitor
µF
4.0
VAC
440
Coil
Aluminum plate fin / Copper tube
Rows
1
Fin pitch
mm
1.3
Face area
m2
0.506
External Finish
Acrylic baked-on enamel finish
Heat
Exch. Coil
Compressor
Fan & Fan Motor
Outdoor Unit
SAP – CM1621GA
6
Содержание SAP-CM1621GA